Electric control box

M COMP

OPERATING INSTRUCTION

1. Type

2. Operating conditions

- Mains supply 220-240V  50/60 Hz
- Rated insulation voltage: 400 Vac
- Maximum thermal protection: da 4 a 18A
- Rated short-time withstand current: 1,5 kA
- Rated conditional short-circuit current: 1 kA
- Environment: B
- Ambient temperature from -5 °C to +40 °C.
- Relative humidity: 20%÷90% without condensation
- Protection IP 44.
- Dimensions 220x210x110, weight 0,92 kg.
- Standards: IEC/EN 60439-1

3. Constuction

Control  box  for  control  and  protection  of
submersible, single-phase motors.
Protection  is  provided  by  means  of  a  main  bi-
polar  switch  with  a  phase  protected  against
overload by means of a thermal element.

Materials

- Thermoplastic case
- Luminous  main  bi-polar  switch  with  1  pole

protected against thermal overload

- Electronic card, containing:

• Terminals for connecting the power line
• Terminals for connecting the motor
• Terminals  for  connecting  pressure  switch  or

float switch

• Cable for connecting the main bi-polar switch
• Cable for connecting the capacitor

- Capacitor
- Cable glands

4. Installation

The  electric  control  panel  must  be  fastened  by
using the relevant holes on the back.
During  installation  do  not  damage  the  electronic
cards  and  the  other  electrical  components  found
inside of the box.
Provide  for  enough  space  all  around  the  control
panel for natural cooling.
Do not install the control panel in places exposed
to direct sunlight or near sources of heat.

5. Electrical connection

Electrical connection must be carried out
by  a  qualified  electrician  in  accordance
with local regulations.

Follow all safety standards.
The unit must be properly earthed (grounded). 

Follow  the  instructions  in  the  wiring  diagram
hereto attached.

Once  the  electrical  connection  has  been
completed,  remove  any  pieces  of  wire,  sheath,
washers  or  any  other  foreign  bodies  that  may  be
found inside the electric control panel.

5.1. Capacitor

Fasten  the  capacitor  in  the  suitable  seat
through the supplied clamp and connect it
through the terminals.

6. Starting

When the control unit is turned on, the pump is on
STOP.  Switching  on  the  main  bi-polar  switch  the
pump stars.

7. Operation

7.1. Standard operation

Control box for control of a single-phase motor.
The pump can work automatically with the signals
from  the  pressure  switch  (pressure  circuit)  or  a
float switch (tank filling). When one of this signals
is installed, use the supplied M16 cable gland.
To fill a storage tank, remove bridge on terminals

and connect the brown-black leads of the float

switch to the control box terminals.

Note  1:  when  the  maximun  current  of
the float switch is less than the nominal
current  of  the  pump,  the  float  switch
has to connect to LVBT electronic card
(on request).

7.2. Operating 

with 

LVBT

electronic card

Control  box  for  control  of  a  single-phase  motor
with  LVBT  electronic  card.  Protects  submersed
pumps against dry-running.

M COMP  7 - 30

Maximum current 7A

Capacitor 30 µF - 450Vc

COMP series 

Single-phase power

M COMP 4-16
M COMP 4-20
M COMP 5-20
M COMP 5-25
M COMP 6-16
M COMP 6-20
M COMP 6-30
M COMP 6-35
M COMP 7-20
M COMP 7-25
M COMP 7-30
M COMP 8-25
M COMP 8-30

M COMP 10-25
M COMP 10-30
M COMP 10-35
M COMP 10-40
M COMP 12-35
M COMP 12-40
M COMP 12-50
M COMP 12-60
M COMP 12-70
M COMP 14-50
M COMP 16-60
M COMP 16-70
M COMP 18-70

Summary of Contents for M COMP 4-16

Page 1: ...MP ISTRUZIONI ORIGINALI PER L USO P 468 01 I Pagina 2 Italiano ORIGINAL OPERATING INSTRUCTIONS P 468 01 GB Page 4 English INSTRUCTIONS ORIGINALES POUR L UTILISATION P 468 01 F Page 6 Fran ais INSTRUCC...

Page 2: ...Eseguire il collegamento a terra Rispettare le indicazioni riportate sullo schema elettrico allegato Dopo il collegamento elettrico eliminare eventuali spezzoni di filo guaine rondelle o altri corpi e...

Page 3: ...immer ruotato tutto in senso antiorario a 12 minuti con trimmer ruotato tutto in senso orario led verde acceso consenso al funzionamento led rosso acceso mancanza acqua nel pozzo led verde e rosso spe...

Page 4: ...ordance with local regulations Follow all safety standards The unit must be properly earthed grounded Follow the instructions in the wiring diagram hereto attached Once the electrical connection has b...

Page 5: ...mer TIME from 0 mins with the timer turned fully in the counter clockwise direction to 12 mins with the timer turned fully in the clockwise direction Green led on operation enabled Red led on no water...

Page 6: ...uivre les normes de s curit Effectuer le branchement la terre Respecter les indications report es sur le sch ma lectrique joint Apr s le branchement lectrique liminer les ventuels bouts de fils gaines...

Page 7: ...ent dans le sens inverse des aiguilles d une montre jusqu 12 minutes avec le potentiom tre de temporisation dirig int gralement dans le sens des aiguilles d une montre LED verte sur on en fonctionneme...

Page 8: ...tricista calificado en el respeto de las disposiciones locales Observar las normas de seguridad Ejecutar la conexi n a tierra Respetar las indicaciones que aparecen en el esquema el ctrico adjunto Des...

Page 9: ...e la bomba de 0 minutos con trimmer girado completamente en sentido antihorario a 12 minutos con trimmer girado completamente en sentido horario led verde encendido consentimiento para el funcionamien...

Page 10: ...zuf hren Befolgen Sie die Sicherheitshinweise Die Erdung ausf hren Beachten Sie die auf dem beigef gten Schaltplan aufgef hrten Hinweise Nach dem elektrischen Anschlie en sind eventuelle Kabelreste Sc...

Page 11: ...ehtem Trimmer bis 12 Minuten bei ganz im Uhrzeigersinn gedrehten Trimmer gr nes Led leuchtet Betrieb freigegeben rotes Led leuchtet Wasser fehlt in der Grube gr nes und rotes Led ausgeschaltet Taktgeb...

Page 12: ...MP 7 30 7A 30 F 450Vc PFC M COMP 4 16 M COMP 4 20 M COMP 5 20 M COMP 5 25 M COMP 6 16 M COMP 6 20 M COMP 6 30 M COMP 6 35 M COMP 7 20 M COMP 7 25 M COMP 7 30 M COMP 8 25 M COMP 8 30 M COMP 10 25 M COM...

Page 13: ...2 2 MAX MAX 0 12 LVBT 3 MAX COM TIME LVBT 0 12 8 8 1 LVBT LVBT 230 MAX MIN COM 8 1 30 240 SENS 2 5 50 10 TIME 0 12 8 2 MIN MAX 2x0 75 2 9 MAX MIN COM C M A Stop Start 4 70 1207 3 MAX MIN COM C M A St...

Page 14: ...dicators off timer has been triggered LED verte sur on en fonctionnement LED rouge sur on pas d eau dans le puits Voyants des LED rouge et verte off le minuteur s est d clench led verde encendido oper...

Page 15: ...flotteur Nivostato Schwimmer Pressostato Pressure switch Pressostat Presostato Druckw chter Galleggiante Nota 1 paragrafo 7 1 Float switch Note 1 paragraph 7 1 Interrupteur flotteur Note 1 paragraphe...

Page 16: ...onsability for conformity with the standards laid down therein DECLARATION OF CONFORMITY I GB Montorso Vicentino 11 2010 Il Presidente Licia Mettifogo DECLARATION DE CONFORMITE Nous CALPEDA S p A d cl...

Reviews: