background image

6   |   

P a g e

   

   

System   Sizing   

All    CALMAG    YORKSHIRE    LIMITED    UV    systems    are    rated    for    a    specific    flow    rate    under    specific    water    quality   

parameters.   The   equipment   has   been   designed   to   ensure   that   the   appropriate   dose   will   be   delivered   provided   all   

parameters   are   followed.   PLEASE   NOTE   that   the   flow   rate   for   each   system   can   be   higher   or   lower   than   what   the   

system    is    rated    for    however    this    will    change    the    dose    level    that    the    system    will    deliver.    A    lower    flow    is    not    a   

concern   as   the   dose   will   increase   however   a   higher   flow   rate   will   decrease   the   dose   and   therefore   compromise   the   

microorganism   inactivation.   

It    is    important    to    know    the    maximum    flow    rate    that    your    water    system    delivers.        If    you    do    not    have    this   

information   you   can   simply   fill   a   1   gallon   bucket   with   water   and   time   how   long   it   takes   to   fill   up.   This   will   be   the   

maximum   flow   rate   for   the   home.      The   appropriate   Calmag   UV   unit   should   then   be   chosen.         

PLEASE   NOTE:      It   is   always   better   to   oversize   your   system   then   to   undersize.   For   example,   if   your   pump   delivers   60   

litres   per   minute   it   is   recommended   to   install   the   CALULTRA   79   UV   unit.   There   will   be   occasions   where   your   home   

is   using   water   at   the   pump’s   maximum   capacity.   

   

Location   

   

Step   1:   Find   a   suitable   location   to   mount   the   UV   

unit.    In    choosing    your    location    ensure    the   

controller    is    located    within    5    feet    of    a    ground   

fault   circuit   interrupter   (GFCI)   and   that   there   is   

easy   access   to   the   main   cold   water   line   prior   to   

any    branch    lines    and    before    the    hot    water   

heater.    If    you    have    any    other    water    treatment   

equipment,    such    as    a    water    softener    or    water   

filter,    ensure    that    the    UV    is    the    last    piece    of   

treatment    equipment.    PLEASE    NOTE:    All   

CALMAG    YORKSHIRE    LIMITED    UV    disinfection   

systems   are   intended   for   indoor   use   only   as   they   

should   not   be   exposed   to   the   elements.   

   

Step    2:    Your    system    includes    mounting   

hardware    for    both    the    UV    unit    and    the   

controller.    If    the    supplied    fittings    are    not   

compatible   with   the   structure   in   which   you   are   

mounting   the   device,   please   ensure   you   use   the   

correct   fittings.   

   

Step   3:   To   facilitate   lamp   removal,   ensure   there   

is    enough    space    at    the    lamp    connector    end    to   

safely   remove   the   UV   lamp   and/or   quartz   sleeve   

(a    space    equal    to    the    length    of    the    unit    will   

suffice)   (see   Figure   1.).   

   

   

   

   

   

   

Figure   1.      Lamp   Removal   Spacing   

   

Summary of Contents for CALULTRA 12

Page 1: ...Remember don t guess ASK Calming troubled waters...

Page 2: ...ter supply with a UV system gives you reassurance that your family will have access to safe drinking water throughout your entire home with no chance of microbiological contamination This is chemical...

Page 3: ...on Controller Overview Page 12 Operation Power up Sequence Page 13 Operation Remote Alarm Module Check Page 14 Operation Operational Screens Page 14 Operation UV Intensity Page 15 Operation Lamp Count...

Page 4: ...ed to be installed indoors and away from leaking plumbing DO NOT plug the unit in if the system or any of the components are wet 9 The disinfection system should be directly installed into a ground fa...

Page 5: ...mendations You can have your water tested at a private analytical laboratory or contact your local council for advice in regards to your local environmental health officer It is always recommended to...

Page 6: ...litres per minute it is recommended to install the CALULTRA 79 UV unit There will be occasions where your home is using water at the pump s maximum capacity Location Step 1 Find a suitable location t...

Page 7: ...or so that the rated flow of your particular CALMAG YORKSHIRE LIMITED system is not exceeded and the UV dose is not compromised The flow restrictor should be installed on the outlet port of the unit S...

Page 8: ...P a g e Installation example unit connect ASSEMBLED ring installation unit unit ring unit unit...

Page 9: ...ly and check for leaks Make sure the by pass valves are functioning properly and that the water is flowing through the unit The most common leak is from the O ring not making a proper seal on the unit...

Page 10: ...d Screw Connection Step 17 Your system is now ready to be plugged into the appropriate GFCI protected outlet Plug the unit in and refer to the System Disinfection section before any water is allowed t...

Page 11: ...inlet shut off valve shut this valve off to prevent water flow through the system If there is no inlet shut off valve turn off main water inlet valve and turn of water pump if you have one Step 2 Disc...

Page 12: ...rew counterclockwise the sensor nut from the unit and pull the sensor slowly out of the sensor port Step 6 Holding the sensor in your hand wipe the flat portion sensor face of the sensor with isopropy...

Page 13: ...at the end of 12 months to replace the ultra violet bulb The Calmag Home Screen will then constantly scroll from right to left indicating that the unit is functioning correctly If the controller butt...

Page 14: ...the front of the controller UV Intensity only for units equipped with a UV sensor If your system is equipped with a UV sensor the UV Output screens will indicate the level of UV intensity that is bei...

Page 15: ...he flow of water if a solenoid valve is installed on the system Lamp Countdown Sequence The UV unit counts down the number of days until a lamp change is required The operation is as follows Once the...

Page 16: ...lamp To perform this reset you must firmly depress the button on the front of the controller and then manually plug the power cord back into the wall outlet initiating power to the unit Keep holding...

Page 17: ...Assuming the system has an optional 4 20 mA Module installed if at any time during the operation of the system a 4 20 mA module fails the controller will return both an audible and visual signal indi...

Page 18: ...imply press the control button twice and the QR code screen will appear as follows Expansion Modules As shown earlier in this manual the CalUltra controllers incorporate an Infinite Expandability Port...

Page 19: ...MODULE Allows for a 4 20mA signal transfer of the UV output to a remote device such as a data logger or computer Simply plug the supplied cable into any female IEP connections Two screw terminals are...

Page 20: ...lug Type British Standard BS1363 Lamp Watts 15 22 39 42 Power watts 20 30 49 51 Replacement Lamp BULB B12 BULB B22 BULB B41 BULB B79 Replacement Sleeve SLEEVE QS12 SLEEVE QS22 SLEEVE QS41 SLEEVE QS79...

Page 21: ...mitations of Warranty as outlined below CALMAG YORKSHIRE LIMITED s liability under this warranty shall be limited to repairing or replacing at CALMAG YORKSHIRE LIMITED s discretion without charge any...

Page 22: ...ng the product Any defective product to be returned to CALMAG YORKSHIRE LIMITED must be sent carriage prepaid documentation supporting the warranty claim and or a Goods Return Number must be included...

Page 23: ...23 P a g e...

Page 24: ...24 P a g e Sandbeds Keighley Tel lmagltd com www calmagltd com Remember don t guess ASK Calming troubled waters Rev11 12...

Reviews: