LEVEL A
Function
Options
[Factory settings] shown in brackets
Linear Input Scaling
Please read in conjunction with Linear Input Set-up Procedure on page 6.
An.hi
-1999 to 9999
[1000]
Adjusts required scale maximum
An.Lo
-1999 to 9999
[0]
Adjusts required scale minimum
hi.in
0.1 to 50.0
[50.0]
Configure input maximum
Lo.in
0.0 to 49.9
[10.0]
Configure Input minimum
This setting must be at least 0.1 less than the setting for
hi.in
above.
Note:
Refer to Linear Input conversion factors detailed in the Set-up Procedure on page 6.
dECP
000.0 to 00.00
[0000]
Scale resolution
NB
. Once the
Linear Input
option has been selected, the setting here over-rides the scale
resolution setting
di.SP
in Level 2 and will affect the following display readings:
Level A:
An.hi
;
An.Lo
;
Set.3
;
hYS.3
Level 1:
bAnd
;
ofSt
;
SPrr
;
SEt2
;
bnd.2
Level 2:
hiSC
;
LoSC
Level 3:
SPAn
;
ZEro
;
rEAd
;
tECh
SP3 SETTINGS
SP3.A [nonE]
dV.hi dV.lo bAnd FS.hi FS.Lo EoP
Main SP3 operating mode
SP3.b [nonE]
LtCh hoLd Lt.ho
Subsidiary SP3 operating mode
SEt.3
0 to 2500
[0]
SP3 setpoint adjustment
hyS.3
0.1 to 100% of hiSC
[20]
Set SP3 hysteresis
10
LEVL A
✢
✢
Function
Options
[Factory settings] shown in brackets
brn.3 [uPSC]
uPSC or dnSC
Sensor burn-out / break protection
Select upscale or downscale
rEV.3 [3d]
3d or 3r
Reverse SP3 output mode
Select direct or reverse operation
Will be affected by
dECP
settings in Level A
✢
English