background image

8

INPUT SELECTION AND RANGING

dI.SP [1]     

0.1

Select display resolution: for display of process value, setpoint,

OFSt, Set.2, hi.SC, LoSC

.

hi.SC 

[sensor maximum] 

sensor maximum 

°C/°F/units

Set full scale

Lo.SC

[sensor minimum] 

sensor minimum 

°C/ºF/units

Set scale minimum (default 0°C/32°F or 0 units)

inPt 

Select input sensor  

[nonE]

(See 

SENSOR SELECTION

table, page 22)

NB. If 

Linear Input

selected, start configuration from 

Level A

.

unit  [nonE]  

°C   °F  bAr   Psi  Ph  rh SEt

Select required operating unit from above options

LEVEL 3

OUTPUT CONFIGURATION

Note 1

:

Read only’ after initial configuration. 

rSET ALL

full reset to factory settings

required to change 

SP1.d  

subsequently.

Note 2

: Depending on the Model, 

SP1

and 

SP2

may be fitted with any of three output

types,

RLY

SSd

or 

Analogue

(Specification on page 11/12) where appropriate,

these must be allocated during initial configuration. 

SP3

is always fitted with 

RLY

.

Output Options Table

Model

SP1 Output

SP2 Output

SP3 Output

95111P

RLY

RLY

RLY

95001P

SSd

RLY

RLY

RLY

SSd

RLY

95221P

SSd

SSd

RL

Y

*95X11P

AnLG

RLY

RLY

RLY

AnLG

RLY

*95X21P

AnLG

SSd

RLY

SSd

AnLG

RLY

* Substitute for X in table above, Analogue options B = 4–20mA, C = 0–5V, D = 0–10V

Will be affected by 

dECP

settings in Level A

Re-transmission

* These models above offer the option of using the analogue output for 

Re-transmission

.

Select 

bAnd

or

bnd.2

value in 

LEVL 1

to equal the full range setting in 

LEVL A

and if

using SP1 output, set 

int.t

and 

dErt.t

in 

LEVL 1

to off.

Example: Set-Up using a Model 95B11P to Re-transmit the 4-20 mA input, scaled 0 to 100 
units. SP1 relay is used as the control output and SP2 analogue output is used for re-
transmission.

Note

: Read in conjunction with Linear Input Set-up Procedure on page 6.

Function      

Options

[Factory settings] shown in brackets

From initial power-up;

Set 

inPt nonE

to 

inPt Lin

unit nonE

to 

unit SEt 

(for example)

SP1.d nonE

to 

SP1.d rLY

To scale the input, select 

LEVL A

, then:

Set 

dECP

to 

000.0

(e.g. required resolution)

An.hi

to 

100.0

An.Lo

to 

0.0

hi.in

to 

50

(ie 20mA)

Lo.in

to 

10

(ie 4mA)

To align SP2 analogue re-transmission with SP1 control output, select LEVL 2 then:

Set 

SP2.A

to 

FS.hi

And in LEVL.1

Set 

SEt.2

to 

50

(ie 50% of display range)

bnd.2

to 

100

(ie 100% of display range)

Finally, set SP1 setpoint value as required for process to start.

Using SP1 output for re-transmission

Set 

int.t

to off

dErt

to off

rev.d

to 

1d.2d

to invert SP1 output

SP1 Setpoint

to

midscale

burn  

Sensor burn-out/break protection

Caution: 

Settings affect fail safe state.

SP1

SP2

[uP.SC]

Upscale

Upscale

dn.SC

Downscale

Downscale

1u.2d 

Upscale

Downscale

1d.2u

Downscale

Upscale

Retransmission range is limited to the sensor full scale value (Example RTD = 400C/752F).

LEVL 3

LEVEL 2 CONTINUED

English

Summary of Contents for 9500P

Page 1: ...Users Manual CAL Controls CAL 9500P Programmable Process Controller E n g l i s h F r a n a i s D e u t s c h I t a l i a n o E s p a o l...

Page 2: ...lay Setpoint value or program selection Green LED Setpoint 1 output indicator Upper Red LED Setpoint 2 output indicator Lower Red LED Setpoint 3 output indicator Green Display Process variable or Func...

Page 3: ...ec 25 sec Derivative approach 0 5 to 5 0 x bAnd 1 5 Cycle time or on off On off 0 1 to 81 sec 20 sec Offset manual reset 0 to 50 x bAnd In t off Setpoint lock SP1 Off on Adjust SP2 setpoint sensor ful...

Page 4: ...lication Re tuning after a large setpoint change Tuning multi zone and or heat cool applications Notes DAC is not re adjusted by Tune at setpoint Proportional Cycle Time can be pre selected before run...

Page 5: ...operate as an alarm from SP2 A in Level 2 and set the alarm setting in SEt 2 Level 1 Configure SP3 alarm mode SP3 A and setting SEt 3 in Level A The alarms will be individually triggered when the pro...

Page 6: ...range 10 to 50 mV using multiplier of 2 5 When using a transducer with an output less than 4 20mA the input maximum and minimum mV values can be calculated using the same multiplier Models with 0 to...

Page 7: ...t 0 to C F units 0 SP1 offset manual reset 50 bAnd Applicable in proportional and ON OFF mode with integral disable Int t oFF SP LK oFF on Lock main setpoint Locks the setpoint preventing unauthorised...

Page 8: ...ion of using the analogue output for Re transmission Select bAnd or bnd 2 value in LEVL 1 to equal the full range setting in LEVL A and if using SP1 output set int t and dErt t in LEVL 1 to off Exampl...

Page 9: ...through UEr in level 3 Press and hold and for 10 seconds Enter level 4 at Lock release and together Display reads LoCK nonE Program security using Lock nonE Select from three Lock options Press and h...

Page 10: ...Input option has been selected the setting here over rides the scale resolution setting di SP in Level 2 and will affect the following display readings Level A An hi An Lo Set 3 hYS 3 Level 1 bAnd of...

Page 11: ...to another that it will replace For safety reasons three modes of recovery from a power failure are available These either automatically Re start the Program from the beginning Continue it from where...

Page 12: ......

Page 13: ...3 SEG 4 SEG 5 PROG 3 SEG 1 SEG 2 SEG 3 SEG 4 STOP 30 SPRR 55 T SP 30 EXAMPLE PROGRAM Temp Time See segment configuration of this program detailed on page 18 Ramp Function Rate 105 deg hour Target setp...

Page 14: ...d program Paste only appears after a program is copied To add new program press once Add new programs at top of existing menu Select the required program number Default 1 Memory used Select program mo...

Page 15: ...To select operational mode of each segment Default Ramp SINT 10 PCYC 1 SUB P NONE SPRR 100 Important note Up button must be used after selecting the segment type to confirm it s selection Adjusts ram...

Page 16: ...d at Call above Edit dEL Delete segment Edit inS Insert new segment FUNCTION LIST LEVEL P PROGRAMMER LEVEL P Access Level P from Level 1 Press and hold Function Settings Factory settings shown in brac...

Page 17: ...2E 3E SP2A and SP3A energised to mark event 2d 3E SP2A de energised SP3A energised to mark event To Return to LEVL P Press and hold To Read Programmer memory used USEd Press and together in LEVL P Pro...

Page 18: ...7 T SP 85 T SP 30 HB V OFF E OP NONE PROG 3 Program settings for functions run FAiL St U and SPru not shown are all set to Default Program Segment Configuration See Program 3 illustrated on page 13 KE...

Page 19: ...ved when handling the controller outside it s sleeve DIMENSIONS Bezel Behind Panel Overall Behind panel Width Height Width Height Length Length 51 0 51 0 44 8 44 8 116 2 106 7 Dimensions in mm include...

Page 20: ...ctors simultaneously A clear instruction shall be provided not to position the equipment so that it is difficult to operate the disconnecting device EMC Immunity EMC immunity may be improved by fittin...

Page 21: ...es 9 5 P B 9 5 P C 9 5 P D RTD PT100 3 wire OUTPUT HARDWARE OPTIONS TERMINATIONS 20 21 22 23 24 17 18 19 20 21 22 23 24 17 18 19 20 21 22 23 24 17 18 19 20 21 22 23 24 17 18 19 20 21 22 23 24 17 18 19...

Page 22: ...range 0 to 50mV Applicable to all inputs SM sensor maximum Calibration accuracy 0 25 SM 1 C Sampling frequency input 10Hz CJC 2 sec Common mode rejection Negligible effect up to 140dB 240V 50 60Hz Ser...

Page 23: ...id if the unit shows evidence of being tampered with or subjected to excessive heat moisture corrosion or other misuse 3 Components which wear or damage with misuse are excluded e g relays 4 CAL Contr...

Page 24: ...4 0 1462 436161 Fax 44 0 1462 451801 email support cal controls co uk http www cal controls com CAL Controls Inc 1117 S Milwaukee Avenue Libertyville IL 60048 USA Tel 847 680 7080 Fax 847 816 6852 ema...

Reviews: