Cairox AOYG-KQTA Installation Manual Download Page 8

En-8

Flare nut [mm (in.)]

Tightening torque [N·m (kgf·cm)]

6.35 (1/4) dia.

16 to 18 (160 to 180)

9.52 (3/8) dia.

32 to 42 (320 to 420)

12.70 (1/2) dia.

49 to 61 (490 to 610)

15.88 (5/8) dia.

63 to 75 (630 to 750)

19.05 (3/4) dia.

90 to 110 (900 to 1100)

 Handling precautions for the valves

•  Mounted part of blank cap is sealed for protection.
•  Fasten blank cap tightly after opening valves.

Table A

Blank cap [mm (in.)]

Tightening torque [N·m (kgf·cm)]

6.35 (1/4)

20 to 25 (200 to 250)

9.52 (3/8)

20 to 25 (200 to 250)

12.70 (1/2)

28 to 32 (280 to 320)

15.88 (5/8)

30 to 35 (300 to 350)

19.05 (3/4)

35 to 40 (350 to 400)

Operating the valves

•  Use a hexagon wrench (size 4 mm).

• Opening

(1)  Insert the hexagon wrench into the valve shaft, and turn it 

counterclockwise.

(2)  Stop turning when the valve shaft can no longer be turned. 

(Open position)

• Closing

(1)  Insert the hexagon wrench into the valve shaft, and turn it clockwise.

(2)  Stop turning when the valve shaft can no longer be turned. 

(Closed position)

Opening direction

Hexagon wrench

Seal (blank cap 
installation portion)

Liquid pipe

Gas pipe

Opening direction

 3.6. Sealing test

 WARNING

•  Before operating the compressor, install the pipes and securely connect them. 

Otherwise, if the pipes are not installed and if the valves are open when the compres-
sor operates, air could enter the refrigeration cycle. If this happens, the pressure in the 
refrigeration cycle will become abnormally high and cause damage or injury.

•  After the installation, make sure there is no refrigerant leakage. If the refrigerant 

leaks into the room and becomes exposed to a source of 

fi

 re such as a fan heater, 

stove, or burner, it produces a toxic gas.

•  Do not subject the pipes to strong shocks during the sealing test. It can rupture the 

pipes and cause serious injury.

 CAUTION

•  Do not block the walls and the ceiling until the sealing test and the charging of the 

refrigerant gas have been completed.

•  For maintenance purposes, do not bury the piping of the outdoor unit.

After connecting the pipes, perform a sealing test.

(1)   Make sure that the 3-way valves are closed before performing a sealing test.
(2)   Pressurize nitrogen gas to 4.15 MPa to perform the sealing test.
(3)   Add nitrogen gas to both the liquid pipes and the gas pipes.
(4)   Check all 

fl

 ared and brazed connections. Then, check that the pressure has not 

decreased.

(5)   Compare the pressures after pressurizing and letting it stand for 24 hours, and 

check that the pressure has not decreased.
*  When the outdoor air temperature changes 5 °C, the test pressure changes 

0.05 MPa. If the pressure has dropped, the pipe joints may be leaking.

(6)   If a leak is found, immediately repair it and perform the sealing test again.
(7)   After completing the sealing test, release the nitrogen gas from both valves.
(8)   Release the nitrogen gas slowly.

•  When using conventional 

fl

 are tools to 

fl

 are R410A pipes, the dimension A should 

be approximately 0.5 mm more than indicated in the table (for 

fl

 aring with R410A 

fl

 are tools) to achieve the speci

fi

 ed 

fl

 aring. Use a thickness gauge to measure the 

dimension A.

Width across 

fl

 ats

Pipe outside 

diameter [mm (in.)]

Width across 

fl

 ats

of Flare nut [mm]

6.35 (1/4)

17

9.52 (3/8)

22

12.70 (1/2)

26

15.88 (5/8)

29

19.05 (3/4)

36

 Bending pipes

 

CAUTION

•  To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of 

curvature of 100 mm to 150 mm.

•  If the pipe is bent repeatedly at the same place, it will break.

•  If pipes are shaped by hand, be careful not to collapse them.
•  Do not bend the pipes at an angle of more than 90°.
•  When pipes are repeatedly bent or stretched, the material will harden, making it 

dif

fi

 cult to bend or stretch them anymore.

•  Do not bend or stretch the pipes more than three times. 

 Connecting pipes

 

CAUTION

•  Be sure to install the pipe against the port on the indoor unit and the outdoor unit 

correctly. If the centering is improper, the 

fl

 are nut cannot be tightened smoothly. If 

the 

fl

 are nut is forced to turn, the threads will be damaged. 

•  Do not remove the 

fl

 are nut from the outdoor unit pipe until immediately before 

connecting the connection pipe.

•  After installing the piping, make sure that the connection pipes do not touch the 

compressor or outer panel. If the pipes touch the compressor or outer panel, they 
will vibrate and produce noise.

(1)   Detach the caps and plugs from the pipes. 
(2)   Center the pipe against the port on the outdoor unit, and then turn the 

fl

 are nut by 

hand.

(3)   Tighten the 

fl

 are nut of the connection pipe at the outdoor unit valve connector.

3-way valve (Liquid)

3-way valve (Gas)

Flare nut

Connection pipe
(Liquid)

Flare nut

Connection pipe
(Gas)

(4)   After tightening the 

fl

 are nut by hand, use a torque wrench to fully tighten it.

 

CAUTION

•  Hold the torque wrench at its grip, keeping it in a right angle with the pipe, in order 

to tighten the 

fl

 are nut correctly.

• Fasten a 

fl

 are nut with a torque wrench as instructed in this manual. If fastened too 

tight, the 

fl

 are nut may be broken after a long period of time and cause a leakage of 

refrigerant.

•  Outer panel may be distorted if fastened only with a wrench. Be sure to 

fi

 x the 

elementary part with a spanner and fasten with a wrench. (Refer to the following 

fi

 gure.)

•  Do not apply force to the blank cap of the valve or hang a wrench, etc., on the cap. It may 

cause leakage of refrigerant.

90°

Flare nut

Torque 
wrench

Holding 
wrench

Torque wrench

To prevent gas leakage, coat the 

fl

 are surface with refrigerator oil.

9379069953_IM.indb   8

9379069953_IM.indb   8

5/24/2019   9:59:19 AM

5/24/2019   9:59:19 AM

Summary of Contents for AOYG-KQTA

Page 1: ...Children should be supervised to ensure that they do not play with the appliance CAUTION For the air conditioner to work appropriately install it as written in this manual This product must be instal...

Page 2: ...copper pipe work If a leak is suspected all naked flames shall be removed extinguished If a leakage of refrigerant is found which requires brazing all of the refrigerant shall be recovered from the sy...

Page 3: ...issioning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed...

Page 4: ...the units are further apart than this correct operation cannot be guaranteed Single type installation Capacity Btu h class 30 000 1 36 000 45 000 54 000 Pipe diameter Liquid Gas Standard mm in 9 52 3...

Page 5: ...rom rain or direct sunlight If the outdoor unit must be installed in an area within easy reach of the general pub lic install as necessary a protective fence or the like to prevent their access Instal...

Page 6: ...ations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concrete blocks The foundation shall support the legs...

Page 7: ...Slit Fig B Fig C 3 5 2 Pipe connection Brazing CAUTION If air or another type of refrigerant enters the refrigeration cycle the internal pressure in the refrigeration cycle will become abnormally high...

Page 8: ...ealing test again 7 After completing the sealing test release the nitrogen gas from both valves 8 Release the nitrogen gas slowly When using conventional flare tools to flare R410A pipes the dimension...

Page 9: ...wires make sure the power supply is off Never touch electrical components immediately after the power supply has been turned off Electrical shock may occur After turning off the power always wait 10...

Page 10: ...l will be displayed and the unit will be inoperable 3 8 1 How to connect wiring to the terminal Caution when wiring cable When stripping off the coating of a lead wire always use a special tool such a...

Page 11: ...connect it securely Firmly secure cable clamp so wire terminations will not receive external stress Connection cable Power supply cable Indoor unit Earth Ground Three phase type Terminal blocks Use t...

Page 12: ...re control will not activate during test operation continuous operation If a knocking sound can be heard in the liquid compression of the compressor stop the unit immediately and then energize the cra...

Page 13: ...cause a serious accident such as electric shock CAUTION Once refrigerant charging is completed be sure to open the valve prior to performing the local settings Otherwise the compressor may fail Discha...

Page 14: ...ing on the operating condition the noise level may not decrease even if the Low noise mode is on Level 2 Blink 9 times 2 Peak cut mode setting Level 1 Blink 9 times The capacity limit can be selected...

Page 15: ...rning to Operation status displays normal operation by pressing the EXIT button once 8 EXTERNAL INPUT AND OUTPUT 8 1 External input 8 1 1 Wiring of connector On Off of the Low noise mode and Peak cut...

Page 16: ...the button on the display board It may cause a serious accident such as electric shock During the pump down operation make sure that the compressor is turned off before you remove the refrigerant pipi...

Page 17: ...ss PUMP DOWN button S130 for 3 seconds or more after 3 minutes after power on POWER MODE ERROR PUMP DOWN LOW NOISE PEAK CUT L1 L2 L3 L4 L5 L6 Sign Lights off Lights on LED display lights on as shown i...

Page 18: ...error Outdoor temp sensor error Blink 2 times Blink 7 times Blink 4 times Heat sink temp sensor error Heat sink temp sensor error Blink 2 times Blink 7 times Blink 7 times Current sensor error Curren...

Reviews: