
En-8
Flare nut [mm (in.)]
Tightening torque [N·m (kgf·cm)]
6.35 (1/4) dia.
16 to 18 (160 to 180)
9.52 (3/8) dia.
32 to 42 (320 to 420)
12.70 (1/2) dia.
49 to 61 (490 to 610)
15.88 (5/8) dia.
63 to 75 (630 to 750)
19.05 (3/4) dia.
90 to 110 (900 to 1100)
Handling precautions for the valves
• Mounted part of blank cap is sealed for protection.
• Fasten blank cap tightly after opening valves.
Table A
Blank cap [mm (in.)]
Tightening torque [N·m (kgf·cm)]
6.35 (1/4)
20 to 25 (200 to 250)
9.52 (3/8)
20 to 25 (200 to 250)
12.70 (1/2)
28 to 32 (280 to 320)
15.88 (5/8)
30 to 35 (300 to 350)
19.05 (3/4)
35 to 40 (350 to 400)
Operating the valves
• Use a hexagon wrench (size 4 mm).
• Opening
(1) Insert the hexagon wrench into the valve shaft, and turn it
counterclockwise.
(2) Stop turning when the valve shaft can no longer be turned.
(Open position)
• Closing
(1) Insert the hexagon wrench into the valve shaft, and turn it clockwise.
(2) Stop turning when the valve shaft can no longer be turned.
(Closed position)
Opening direction
Hexagon wrench
Seal (blank cap
installation portion)
Liquid pipe
Gas pipe
Opening direction
3.6. Sealing test
WARNING
• Before operating the compressor, install the pipes and securely connect them.
Otherwise, if the pipes are not installed and if the valves are open when the compres-
sor operates, air could enter the refrigeration cycle. If this happens, the pressure in the
refrigeration cycle will become abnormally high and cause damage or injury.
• After the installation, make sure there is no refrigerant leakage. If the refrigerant
leaks into the room and becomes exposed to a source of
fi
re such as a fan heater,
stove, or burner, it produces a toxic gas.
• Do not subject the pipes to strong shocks during the sealing test. It can rupture the
pipes and cause serious injury.
CAUTION
• Do not block the walls and the ceiling until the sealing test and the charging of the
refrigerant gas have been completed.
• For maintenance purposes, do not bury the piping of the outdoor unit.
After connecting the pipes, perform a sealing test.
(1) Make sure that the 3-way valves are closed before performing a sealing test.
(2) Pressurize nitrogen gas to 4.15 MPa to perform the sealing test.
(3) Add nitrogen gas to both the liquid pipes and the gas pipes.
(4) Check all
fl
ared and brazed connections. Then, check that the pressure has not
decreased.
(5) Compare the pressures after pressurizing and letting it stand for 24 hours, and
check that the pressure has not decreased.
* When the outdoor air temperature changes 5 °C, the test pressure changes
0.05 MPa. If the pressure has dropped, the pipe joints may be leaking.
(6) If a leak is found, immediately repair it and perform the sealing test again.
(7) After completing the sealing test, release the nitrogen gas from both valves.
(8) Release the nitrogen gas slowly.
• When using conventional
fl
are tools to
fl
are R410A pipes, the dimension A should
be approximately 0.5 mm more than indicated in the table (for
fl
aring with R410A
fl
are tools) to achieve the speci
fi
ed
fl
aring. Use a thickness gauge to measure the
dimension A.
Width across
fl
ats
Pipe outside
diameter [mm (in.)]
Width across
fl
ats
of Flare nut [mm]
6.35 (1/4)
17
9.52 (3/8)
22
12.70 (1/2)
26
15.88 (5/8)
29
19.05 (3/4)
36
Bending pipes
CAUTION
• To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of
curvature of 100 mm to 150 mm.
• If the pipe is bent repeatedly at the same place, it will break.
• If pipes are shaped by hand, be careful not to collapse them.
• Do not bend the pipes at an angle of more than 90°.
• When pipes are repeatedly bent or stretched, the material will harden, making it
dif
fi
cult to bend or stretch them anymore.
• Do not bend or stretch the pipes more than three times.
Connecting pipes
CAUTION
• Be sure to install the pipe against the port on the indoor unit and the outdoor unit
correctly. If the centering is improper, the
fl
are nut cannot be tightened smoothly. If
the
fl
are nut is forced to turn, the threads will be damaged.
• Do not remove the
fl
are nut from the outdoor unit pipe until immediately before
connecting the connection pipe.
• After installing the piping, make sure that the connection pipes do not touch the
compressor or outer panel. If the pipes touch the compressor or outer panel, they
will vibrate and produce noise.
(1) Detach the caps and plugs from the pipes.
(2) Center the pipe against the port on the outdoor unit, and then turn the
fl
are nut by
hand.
(3) Tighten the
fl
are nut of the connection pipe at the outdoor unit valve connector.
3-way valve (Liquid)
3-way valve (Gas)
Flare nut
Connection pipe
(Liquid)
Flare nut
Connection pipe
(Gas)
(4) After tightening the
fl
are nut by hand, use a torque wrench to fully tighten it.
CAUTION
• Hold the torque wrench at its grip, keeping it in a right angle with the pipe, in order
to tighten the
fl
are nut correctly.
• Fasten a
fl
are nut with a torque wrench as instructed in this manual. If fastened too
tight, the
fl
are nut may be broken after a long period of time and cause a leakage of
refrigerant.
• Outer panel may be distorted if fastened only with a wrench. Be sure to
fi
x the
elementary part with a spanner and fasten with a wrench. (Refer to the following
fi
gure.)
• Do not apply force to the blank cap of the valve or hang a wrench, etc., on the cap. It may
cause leakage of refrigerant.
90°
Flare nut
Torque
wrench
Holding
wrench
Torque wrench
To prevent gas leakage, coat the
fl
are surface with refrigerator oil.
9379069953_IM.indb 8
9379069953_IM.indb 8
5/24/2019 9:59:19 AM
5/24/2019 9:59:19 AM