Cairox AOYG-KQTA Installation Manual Download Page 13

En-13

5. FINISHING

 

WARNING

Install the insulated pipes so that they do not touch the compressor.

5.1. Installing insulation

• Install insulation material after conducting “3.6. Sealing test”.
• To prevent condensation and water droplets, install insulation material on the refrigerant 

pipe. (Fig. A)

• Refer to the table to determine the thickness of the insulation material.

Selection of insulation
(Use an insulation material with equal heat transmission rate or below 0.040 
W/(m·k))

Insulation material minimum thickness (mm)

Relative humidity

 70%

 75%

 80%

 85%

Pipe diameter 

(mm)

6.35

8

10

13

17

9.52

9

11

14

18

12.70

10

12

15

19

15.88

10

12

16

20

19.05

10

13

16

21

22.22

11

13

17

22

25.40

11

13

17

22

*  When the ambient temperature and relative humidity exceed 32 °C (DB) and 85% 

respectively, please strengthen the heat insulation of refrigerant pipe.

5.2. Filling with putty

 

WARNING

Fill the piping holes and wiring holes with putty (locally purchased) to avoid any gap 
(Fig. A). If small animals such as insects enter the external unit, a short circuit may be 
caused near electrical components in the service panel.

•  If the outdoor unit is installed at a level that is higher than the indoor unit, the water 

that has condensed in the 3-way valve of the outdoor unit could travel to the indoor 
unit. Therefore, use putty in the space between the pipe and the insulation to prevent 
the entry of water to the indoor units.

Fig. A

Putty

Insulation

6.  HOW TO OPERATE DISPLAY UNIT

6.1. Display unit position

 

WARNING

Never touch electrical components such as the terminal blocks except the button on 
the display board. It may cause a serious accident such as electric shock.

 

CAUTION

•  Once refrigerant charging is completed, be sure to open the valve prior to 

performing the local settings. Otherwise, the compressor may fail.

•  Discharge any static electricity from your body before touching the push buttons. 

Never touch any terminal or pattern of any parts on the control board.

•  The positions of the buttons on the outdoor unit control board are shown in the 

following 

fi

 gure.

•  Various settings can be adjusted by changing push buttons on the board of the outdoor 

unit.

Push buttons

LED display

6.2. Description of display and buttons

•  The printed characters for the LED display are shown below.

S134

S133

S132

S131

S130

LED display part

Button part

Display lamp

Function or operation method

(1) POWER / MODE

Green

Lights on while power on. Local setting in out-

door unit or error code is displayed with blink.

(2) ERROR

Red

Blinks during abnormal air conditioner 

operation. 

(3)  PUMP DOWN 

(L1)

Orange

Lights on during pump down operation.

(4)  LOW NOISE 

(L2, L3)

Orange

Lights on during Low noise mode when local 

setting is activated. (Lighting pattern of L2 and 

L3 indicates low noise level) 

*Refer to the page 14.

(5)  PEAK CUT 

(L4, L5, L6)

Orange

Lights on during Peak cut mode when local 

setting is activated. (Lighting pattern of L4, L5 

and L6 indicates peak cut level) 

*Refer to the page 15.

Button

Function or operation method

S134

MODE

To switch between “Local setting” and “Error code 
display”.

S133

SELECT

To switch between the individual “Local settings” 
and the “Error code displays”.

S132

ENTER

To 

fi

 x the individual “Local settings” and the “Error 

code displays”.

S131

EXIT

To return to “Operation status displays.”

S130

PUMP DOWN

To start the pump down operation.

9379069953_IM.indb   13

9379069953_IM.indb   13

5/24/2019   9:59:20 AM

5/24/2019   9:59:20 AM

Summary of Contents for AOYG-KQTA

Page 1: ...Children should be supervised to ensure that they do not play with the appliance CAUTION For the air conditioner to work appropriately install it as written in this manual This product must be instal...

Page 2: ...copper pipe work If a leak is suspected all naked flames shall be removed extinguished If a leakage of refrigerant is found which requires brazing all of the refrigerant shall be recovered from the sy...

Page 3: ...issioning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed...

Page 4: ...the units are further apart than this correct operation cannot be guaranteed Single type installation Capacity Btu h class 30 000 1 36 000 45 000 54 000 Pipe diameter Liquid Gas Standard mm in 9 52 3...

Page 5: ...rom rain or direct sunlight If the outdoor unit must be installed in an area within easy reach of the general pub lic install as necessary a protective fence or the like to prevent their access Instal...

Page 6: ...ations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concrete blocks The foundation shall support the legs...

Page 7: ...Slit Fig B Fig C 3 5 2 Pipe connection Brazing CAUTION If air or another type of refrigerant enters the refrigeration cycle the internal pressure in the refrigeration cycle will become abnormally high...

Page 8: ...ealing test again 7 After completing the sealing test release the nitrogen gas from both valves 8 Release the nitrogen gas slowly When using conventional flare tools to flare R410A pipes the dimension...

Page 9: ...wires make sure the power supply is off Never touch electrical components immediately after the power supply has been turned off Electrical shock may occur After turning off the power always wait 10...

Page 10: ...l will be displayed and the unit will be inoperable 3 8 1 How to connect wiring to the terminal Caution when wiring cable When stripping off the coating of a lead wire always use a special tool such a...

Page 11: ...connect it securely Firmly secure cable clamp so wire terminations will not receive external stress Connection cable Power supply cable Indoor unit Earth Ground Three phase type Terminal blocks Use t...

Page 12: ...re control will not activate during test operation continuous operation If a knocking sound can be heard in the liquid compression of the compressor stop the unit immediately and then energize the cra...

Page 13: ...cause a serious accident such as electric shock CAUTION Once refrigerant charging is completed be sure to open the valve prior to performing the local settings Otherwise the compressor may fail Discha...

Page 14: ...ing on the operating condition the noise level may not decrease even if the Low noise mode is on Level 2 Blink 9 times 2 Peak cut mode setting Level 1 Blink 9 times The capacity limit can be selected...

Page 15: ...rning to Operation status displays normal operation by pressing the EXIT button once 8 EXTERNAL INPUT AND OUTPUT 8 1 External input 8 1 1 Wiring of connector On Off of the Low noise mode and Peak cut...

Page 16: ...the button on the display board It may cause a serious accident such as electric shock During the pump down operation make sure that the compressor is turned off before you remove the refrigerant pipi...

Page 17: ...ss PUMP DOWN button S130 for 3 seconds or more after 3 minutes after power on POWER MODE ERROR PUMP DOWN LOW NOISE PEAK CUT L1 L2 L3 L4 L5 L6 Sign Lights off Lights on LED display lights on as shown i...

Page 18: ...error Outdoor temp sensor error Blink 2 times Blink 7 times Blink 4 times Heat sink temp sensor error Heat sink temp sensor error Blink 2 times Blink 7 times Blink 7 times Current sensor error Curren...

Reviews: