10.2. Error code check table
DESCRIPTION
REMARK
LED display
POWER/
MODE
ERROR
PUMP
DOWN
LOW NOISE
PEAK CUT
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
Serial communication error
Serial forward transmission error immediately after
operation
Blink
(2 times)
●
Blink
(1 time)
Blink
(1 time)
○
○
●
●
Serial forward transmission error during operation
Blink
(2 times)
●
Blink
(1 time)
Blink
(1 time)
○
●
○
○
Indoor unit capacity error
Indoor unit capacity error
Blink
(2 times)
●
Blink
(2 times)
Blink
(2 times)
○
○
○
●
Indoor unit error
Indoor unit error
Blink
(2 times)
●
Blink
(5 times)
Blink
(15 times)
○
○
○
●
Outdoor unit main PCB error
Outdoor unit PCB model information error
Blink
(2 times)
●
Blink
(6 times)
Blink
(2 times)
○
○
○
●
Inverter PCB error
Inverter error
Blink
(2 times)
●
Blink
(6 times)
Blink
(3 times)
○
○
○
●
IPM error
Trip terminal L error
Blink
(2 times)
●
Blink
(6 times)
Blink
(5 times)
○
○
●
●
Discharge temp. sensor error
Discharge temp. sensor 1 error
Blink
(2 times)
●
Blink
(7 times)
Blink
(1 time)
○
○
○
●
Compressor temp. sensor error
Compressor temp. sensor 1 error
Blink
(2 times)
●
Blink
(7 times)
Blink
(2 times)
○
○
○
●
Outdoor unit Heat Ex. sensor error
Heat Ex. center temp. sensor error
Blink
(2 times)
●
Blink
(7 times)
Blink
(3 times)
○
○
●
○
Outdoor unit Heat Ex. liquid temp. sensor error
Blink
(2 times)
●
Blink
(7 times)
Blink
(3 times)
○
○
●
●
Outdoor temp. sensor error
Outdoor temp. sensor error
Blink
(2 times)
●
Blink
(7 times)
Blink
(4 times)
○
○
○
●
Heat sink temp. sensor error
Heat sink temp. sensor error
Blink
(2 times)
●
Blink
(7 times)
Blink
(7 times)
○
○
○
●
Current sensor error
Current sensor 1 error (stoppage permanently)
Blink
(2 times)
●
Blink
(8 times)
Blink
(4 times)
○
○
○
●
Pressure sensor error
High pressure switch 1 error
Blink
(2 times)
●
Blink
(8 times)
Blink
(6 times)
○
●
○
○
Pressure sensor error
Blink
(2 times)
●
Blink
(8 times)
Blink
(6 times)
○
●
●
○
Trip detection
Trip detection
Blink
(2 times)
●
Blink
(9 times)
Blink
(4 times)
○
○
○
●
Compressor motor control error
Rotor position detection error (stoppage permanently)
Blink
(2 times)
●
Blink
(9 times)
Blink
(5 times)
○
○
○
●
Outdoor unit fan motor 1 error
Duty abnormal
Blink
(2 times)
●
Blink
(9 times)
Blink
(7 times)
○
○
●
●
Outdoor unit fan motor 2 error
Duty abnormal
Blink
(2 times)
●
Blink
(9 times)
Blink
(8 times)
○
○
●
●
4-way valve error
4-way valve error
Blink
(2 times)
●
Blink
(9 times)
Blink
(9 times)
○
○
○
●
Discharge temp. 1 error
Discharge temp. 1 error
Blink
(2 times)
●
Blink
(10 times)
Blink
(1 time)
○
○
○
●
Compressor temp. error
Compressor 1 temp. error
Blink
(2 times)
●
Blink
(10 times)
Blink
(3 times)
○
○
○
●
Pressure error 2
Low pressure error
Blink
(2 times)
●
Blink
(10 times)
Blink
(5 times)
○
○
○
●
IPM error
Temp. error
Blink
(2 times)
●
Blink
(6 times)
Blink
(5 times)
○
○
○
●
Heat sink temp. error
Heat sink temp. error
Blink
(2 times)
●
Blink
(10 times)
Blink
(12 times)
○
○
●
●
Sign “
○
”: Lights off, “
●
”: Lights on