En-6
3.1.2. Multiple outdoor unit installation
• Provide at least 250 mm of space between the outdoor units if multiple units are
installed.
• When routing the piping from the side of an outdoor unit, provide space for the piping.
When the upward area is open
(Unit : mm)
(1) Obstacles at rear only
300
or more
250
or more
(2) Obstacles at front only
1500
or more
250
or more
(3) Obstacles at front and rear
500 or more
1500 or more
250
or more
When an obstruction is present also in the upward area
(Unit : mm)
(1) Obstacles at rear and above
• Up to 3 units can be installed side by side.
• When 4 units or more are arranged in a line, provide the space as shown below.
1500
or more
500 or more
250
or more
Max. 300
1500
or more
3.1.3. Outdoor units installation in multi row
(Unit : mm)
(1) Single parallel unit arrangement
150 or more
600 or more
1500 or more
3000 or more
(2) Multiple parallel unit arrangement
500 or more
600 or more
1500 or more
250 or more
3500 or more
250 or more
NOTES:
• If the space is larger than stated above, the condition will be the same as when there
is no obstacle.
• When installing the outdoor unit, be sure to open the front and left side to obtain
better operation ef
fi
ciency.
3.2. Transporting the unit
WARNING
Do not touch the
fi
ns. Otherwise, personal injury could result.
CAUTION
When carrying the unit, hold the handles on the right and left sides and be careful.
If the outdoor unit is carried from the bottom, hands or
fi
ngers may be pinched.
• Be sure to hold the handles on the sides of the unit. Otherwise, the suction grilles on
the sides of the unit may be deformed.
Handle
Handle
3.3. Mounting the unit
• Install 4 anchor bolts at the locations indicated with arrows in the
fi
gure.
• To reduce vibration, do not install the unit directly on the ground. Install it on a secure
base (such as concrete blocks).
• The foundation shall support the legs of the unit and have a width of 50 mm or more.
• Depending on the installation conditions, the outdoor unit may spread its vibration
during operation, which may cause noise and vibration. Therefore, attach damping
materials (such as damping pads) to the outdoor unit during installation.
• Install the foundation, making sure that there is enough space for installing the
connection pipes.
• Secure the unit to a solid block using foundation bolts. (Use 4 sets of commercially
available M10 bolts, nuts, and washers.)
• The bolts should protrude 20 mm. (Refer to the
fi
gure.)
• If overturning prevention is required, purchase the necessary commercially available
items.
(Unit : mm)
147
AIR
650
143
50
50
16
354
Bolt
20
Nut
Block
CAUTION
• Do not install the outdoor unit in two-stage where the drain water could freeze. Oth-
erwise the drainage from the upper unit may form ice and cause a malfunction of the
lower unit.
• When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe.
If the drain pipe is used, the drain water in the pipe may freeze in extremely cold
climate.
Base
50 mm
or more
• If the unit is installed in a region that is exposed to
high winds, freezing conditions, freezing rain, snow
fall or heavy snow accumulation, take appropriate
measures to protect it from those elements.
To ensure stable operation, the outdoor unit must
be installed on a raised stand or rack, at or above
the anticipated snow depth for the region.
The installation of snow hoods and drift preven-
tion fencing is recommended when blowing and
drifting snow is common to the region.