
En-7
3.4. Drain installation
CAUTION
• Perform drain work in accordance with this Manual, and ensure that the drain water
is properly drained. If the drain work is not carried out correctly, water may drip down
from the unit, wetting the furniture.
• When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe.
If the drain pipe is used, the drain water in the pipe may freeze in extremely cold
weather.
• If you are installing the drain pipe and drain caps,
please provide a working space under the base of
the outdoor unit.
• As the drain water
fl
ows out of the outdoor unit
during heating operation, install the drain pipe and
connect it to a commercial 16 mm hose. (Reverse
cycle model only)
• When installing the drain pipe, plug all the holes
other than the drain pipe mounting hole in the
bottom of the outdoor unit with putty so there is no
water leakage. (Reverse cycle model only)
Drain pipe mounting hole
Base of the outdoor unit
Drain pipe
(Unit : mm)
270
265
170
352
267
49
680
Drain cap mounting hole ×3
Drain pipe mounting
hole ×1
AIR
3.5. Pipe installation
3.5.1. Opening a knock out hole
CAUTION
• Be careful not to deform or scratch the panel while opening the knock out holes.
• To protect the piping insulation after opening a knock out hole, remove any burrs
from the edge of the hole. It is recommended to apply rust prevention paint to the
edge of the hole.
• Pipes can be connected from 4 directions, front, lateral side, rear side and bottom.
(Fig. A)
• When connecting at the bottom, remove the service panel and piping cover on the
front of the outdoor unit, and open the knock out hole provided at the bottom corner
of the piping outlet.
• It can be installed as shown on “Fig. B” cutting out the 2 slits as indicated on “Fig. C”.
(When cutting slits, use a steel saw.)
Fig.
A
Service cover
Front
connection
Bottom
connection
Lateral
connection
Rear
connection
Bottom
connection
Slit
Slit
Fig. B
Fig. C
3.5.2. Pipe connection
Brazing
CAUTION
• If air or another type of refrigerant enters the refrigeration cycle, the internal
pressure in the refrigeration cycle will become abnormally high and prevent the unit
from exerting its full performance.
• Apply nitrogen gas while brazing the pipes. If a pipe is brazed without applying
nitrogen gas, an oxidation
fi
lm will be created.
This can degrade performance or damage the parts
in the unit (such as the compressor or valves).
Nitrogen gas pressure: 0.02 MPa
(= pressure felt suf
fi
ciently on the back of the hand)
• For brazing material, use phosphor copper
that does not require
fl
ux. Do not use
fl
ux to
braze pipes. If the
fl
ux is the chlorine type, it will
cause the pipes to corrode.
Furthermore, if the
fl
ux contains
fl
uoride, it will adversely affect the refrigerant pipe
system such as by degrading the refrigerant.
If
fl
uoride is contained, quality of refrigerant deteriorates and affects the refrigerant
piping system.
Flaring
CAUTION
Do not use mineral oil on a
fl
ared part. Prevent mineral oil from getting into the system
as this would reduce the lifetime of the units.
• Use special pipe cutter and
fl
are tool exclusive for R410A.
(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that the cuttings will not enter the pipe and remove any
burrs.
(3) Insert the
fl
are nut (always use the
fl
are nut attached to the indoor and outdoor
units respectively) onto the pipe and perform the
fl
are processing with a
fl
are tool.
Leakage of refrigerant may result if other
fl
are nuts are used.
(4) Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from
entering the pipes.
Check if [L] is
fl
ared uniformly and
is not cracked or scratched.
B
Pipe
A
Die
Pipe outside diameter
[mm (in.)]
Dimension A [mm]
Dimension B
-
0
0.4
[mm]
Flare tool for R410A,
clutch type
6.35 (1/4)
0 to 0.5
9.1
9.52 (3/8)
13.2
12.70 (1/2)
16.6
15.88 (5/8)
19.7
19.05 (3/4)
24.0
Pressure regulating valve
Cap
Brazing area
Nitrogen gas
9379069953_IM.indb 7
9379069953_IM.indb 7
5/24/2019 9:59:19 AM
5/24/2019 9:59:19 AM