Cairox AOYG-KQTA Installation Manual Download Page 3

En-3

 

CAUTION

8. Removal and evacuation

•  When breaking into the refrigerant circuit to make repairs – or for any other 

purpose –conventional procedures shall be used. 
However, it is important that best practice is followed since 

fl

 ammability is a 

consideration. 
The following procedure shall be adhered to:

• remove refrigerant
•  purge the circuit with inert gas
• evacuate
•  purge again with inert gas
•  open the circuit by cutting or brazing

•  The refrigerant charge shall be recovered into the correct recovery cylinders. 
•  The system shall be “

fl

 ushed” with OFN to render the unit safe. 

•  This process may need to be repeated several times. 
•  Compressed air or oxygen shall not be used for this task.
•  Flushing shall be achieved by breaking the vacuum in the system with OFN and 

continuing to 

fi

 ll until the working pressure is achieved, then venting to atmosphere, 

and 

fi

 nally pulling down to a vacuum. 

•  This process shall be repeated until no refrigerant is within the system. 
• When the 

fi

 nal OFN charge is used, the system shall be vented down to atmo-

spheric pressure to enable work to take place.

•  This operation is absolutely vital if brazing operations on the pipe work are to take 

place.

•  Ensure that the outlet for the vacuum pump is not close to any ignition sources and 

there is ventilation available.

9. Charging procedures

•  In addition to conventional charging procedures, the following requirements shall 

be followed.

-  Ensure that contamination of different refrigerants does not occur when using 

charging equipment. 

  -  Hoses or lines shall be as short as possible to minimize the amount of refriger-

ant contained in them. 

  -  Cylinders shall be kept upright.
  -  Ensure that the refrigeration system is earthed prior to charging the system with 

refrigerant.

  - Label the system when charging is complete (if not already).
  - Extreme care shall be taken not to over

fi

 ll the refrigeration system.

•  Prior to recharging the system it shall be pressure tested with OFN. 
•  The system shall be leak tested on completion of charging but prior to commis-

sioning. 

•  A follow up leak test shall be carried out prior to leaving the site.

10. Decommissioning

•  Before carrying out this procedure, it is essential that the technician is completely 

familiar with the equipment and all its details.

•  It is recommended good practice that all refrigerants are recovered safely.
•  Prior to the task being carried out, an oil and refrigerant sample shall be taken in 

case analysis is required prior to re-use of reclaimed refrigerant.

•  It is essential that electrical power is available before the task is commenced.

a)  Become familiar with the equipment and its operation.
b)  Isolate system electrically.
c)  Before attempting the procedure ensure that:

•  mechanical handling equipment is available, if required, for handling refrig-

erant cylinders;

•  all personal protective equipment is available and being used correctly; 
•  the recovery process is supervised at all times by a competent person; 
•  recovery equipment and cylinders conform to the appropriate standards.

d)  Pump down refrigerant system, if possible.
e)  If a vacuum is not possible, make a manifold so that refrigerant can be re-

moved from various parts of the system.

f)   Make sure that cylinder is situated on the scales before recovery takes place.
g)  Start the recovery machine and operate in accordance with manufacturer’s 

instructions.

h)  Do not over

fi

 ll cylinders. (No more than 80 % volume liquid charge).

i)   Do not exceed the maximum working pressure of the cylinder, even temporarily.
j)   When the cylinders have been 

fi

 lled correctly and the process completed, make 

sure that the cylinders and the equipment are removed from site promptly and 
all isolation valves on the equipment are closed off.

k)  Recovered refrigerant shall not be charged into another refrigeration system 

unless it has been cleaned and checked.

11. Labelling

•  Equipment shall be labelled stating that it has been de-commissioned and emptied 

of refrigerant. 

•  The label shall be dated and signed. 
•  Ensure that there are labels on the equipment stating the equipment contains 

fl

 am-

mable refrigerant.

12. Recovery

•  When removing refrigerant from a system, either for servicing or decommissioning, 

it is recommended good practice that all refrigerants are removed safely.

•  When transferring refrigerant into cylinders, ensure that only appropriate refrigerant 

recovery cylinders are employed.

•  Ensure that the correct number of cylinders for holding the total system charge are 

available. 

•  All cylinders to be used are designated for the recovered refrigerant and labelled 

for that refrigerant (i.e. special cylinders for the recovery of refrigerant). 

•  Cylinders shall be complete with pressure relief valve and associated shut-off 

valves in good working order.

•  Empty recovery cylinders are evacuated and, if possible, cooled before recovery 

occurs.

•  The recovery equipment shall be in good working order with a set of instructions 

concerning the equipment that is at hand and shall be suitable for the recovery of 

fl

 ammable refrigerants.

•  In addition, a set of calibrated weighing scales shall be available and in good work-

ing order.

•  Hoses shall be complete with leak-free disconnect couplings and in good condition.
•  Before using the recovery machine, check that it is in satisfactory working order, 

has been properly maintained and that any associated electrical components are 
sealed to prevent ignition in the event of a refrigerant release. 
Consult manufacturer if in doubt.

•  The recovered refrigerant shall be returned to the refrigerant supplier in the correct 

recovery cylinder, and the relevant Waste Transfer Note arranged. 

•  Do not mix refrigerants in recovery units and especially not in cylinders.
•  If compressors or compressor oils are to be removed, ensure that they have been 

evacuated to an acceptable level to make certain that 

fl

 ammable refrigerant does 

not remain within the lubricant. 

•  The evacuation process shall be carried out prior to returning the compressor to 

the suppliers. 

•  Only electric heating to the compressor body shall be employed to accelerate this 

process. 

•  When oil is drained from a system, it shall be carried out safely.

Explanation of symbols displayed on the indoor unit or outdoor unit.

WARNING

This symbol shows that this equipment uses a 

fl

 ammable 

refrigerant. If the refrigerant is leaked, together with an 
external ignition source, there is a possibility of ignition.

CAUTION

This symbol shows that the Operation Manual should be 
read carefully.

CAUTION

This symbol shows that a service personnel should be 
handling this equipment with reference to the Installation 
Manual.

CAUTION

This symbol shows that there is information included in the 
Operation Manual and/or Installation Manual.

2. PRODUCT SPECIFICATION

 2.1. Installation tools

 WARNING

•  To install a unit that uses R32 refrigerant, use dedicated tools and piping materials that 

have been manufactured speci

fi

 cally for R32(R410A) use. Because the pressure of 

R32 refrigerant is approximately 1.6 times higher than R22, failure to use dedicated 
piping material or improper installation can cause rupture or injury. Furthermore, it can 
cause serious accidents such as water leakage, electric shock, or 

fi

 re.

•  Do not use a vacuum pump or refrigerant recovery tools with a series motor, since it 

may ignite.

Tool name

Contents of change

Gauge manifold

Pressure is high and cannot be measured with a conventional 
(R22) gauge. To prevent erroneous mixing of other refriger-
ants, the diameter of each port has been changed. 
It is recommended the gauge with seals -0.1 to 5.3 MPa 
(-1 to 53 bar) for high pressure. -0.1 to 3.8 MPa (-1 to 38 bar) 
for low pressure.

Charge hose

To increase pressure resistance, the hose material and base 
size were changed. (R32/R410A)

Vacuum pump

A conventional vacuum pump can be used by installing a 
vacuum pump adapter.
(Use of a vacuum pump with a series motor is prohibited.)

Gas leakage detector

Special gas leakage detector for HFC refrigerant R32/R410A.

 Copper pipes

It is necessary to use seamless copper pipes and it is desirable that the amount of residual 
oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or 
discolored portion (especially on the interior surface). Otherwise, the expansion valve or 
capillary tube may become blocked with contaminants.
As an air conditioner using R32(R410A) incurs pressure higher than when using conven-
tional refrigerant, it is necessary to choose adequate materials.

9379069953_IM.indb   3

9379069953_IM.indb   3

5/24/2019   9:59:18 AM

5/24/2019   9:59:18 AM

Summary of Contents for AOYG-KQTA

Page 1: ...Children should be supervised to ensure that they do not play with the appliance CAUTION For the air conditioner to work appropriately install it as written in this manual This product must be instal...

Page 2: ...copper pipe work If a leak is suspected all naked flames shall be removed extinguished If a leakage of refrigerant is found which requires brazing all of the refrigerant shall be recovered from the sy...

Page 3: ...issioning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed...

Page 4: ...the units are further apart than this correct operation cannot be guaranteed Single type installation Capacity Btu h class 30 000 1 36 000 45 000 54 000 Pipe diameter Liquid Gas Standard mm in 9 52 3...

Page 5: ...rom rain or direct sunlight If the outdoor unit must be installed in an area within easy reach of the general pub lic install as necessary a protective fence or the like to prevent their access Instal...

Page 6: ...ations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concrete blocks The foundation shall support the legs...

Page 7: ...Slit Fig B Fig C 3 5 2 Pipe connection Brazing CAUTION If air or another type of refrigerant enters the refrigeration cycle the internal pressure in the refrigeration cycle will become abnormally high...

Page 8: ...ealing test again 7 After completing the sealing test release the nitrogen gas from both valves 8 Release the nitrogen gas slowly When using conventional flare tools to flare R410A pipes the dimension...

Page 9: ...wires make sure the power supply is off Never touch electrical components immediately after the power supply has been turned off Electrical shock may occur After turning off the power always wait 10...

Page 10: ...l will be displayed and the unit will be inoperable 3 8 1 How to connect wiring to the terminal Caution when wiring cable When stripping off the coating of a lead wire always use a special tool such a...

Page 11: ...connect it securely Firmly secure cable clamp so wire terminations will not receive external stress Connection cable Power supply cable Indoor unit Earth Ground Three phase type Terminal blocks Use t...

Page 12: ...re control will not activate during test operation continuous operation If a knocking sound can be heard in the liquid compression of the compressor stop the unit immediately and then energize the cra...

Page 13: ...cause a serious accident such as electric shock CAUTION Once refrigerant charging is completed be sure to open the valve prior to performing the local settings Otherwise the compressor may fail Discha...

Page 14: ...ing on the operating condition the noise level may not decrease even if the Low noise mode is on Level 2 Blink 9 times 2 Peak cut mode setting Level 1 Blink 9 times The capacity limit can be selected...

Page 15: ...rning to Operation status displays normal operation by pressing the EXIT button once 8 EXTERNAL INPUT AND OUTPUT 8 1 External input 8 1 1 Wiring of connector On Off of the Low noise mode and Peak cut...

Page 16: ...the button on the display board It may cause a serious accident such as electric shock During the pump down operation make sure that the compressor is turned off before you remove the refrigerant pipi...

Page 17: ...ss PUMP DOWN button S130 for 3 seconds or more after 3 minutes after power on POWER MODE ERROR PUMP DOWN LOW NOISE PEAK CUT L1 L2 L3 L4 L5 L6 Sign Lights off Lights on LED display lights on as shown i...

Page 18: ...error Outdoor temp sensor error Blink 2 times Blink 7 times Blink 4 times Heat sink temp sensor error Heat sink temp sensor error Blink 2 times Blink 7 times Blink 7 times Current sensor error Curren...

Reviews: