Model 9163
Digital indicator
Page 58
5.3 Errors during measurement mode
If errors occur during measurement use, the "PV" display shows an error code.
Table 3: Error codes and their meanings
Error code
Meaning
Lo
The actual value is less than the lower scale value (parameter
LoS
in menu
INP
)
HI
The actual value is greater than the upper scale value (parameter
Ki S
in menu
INP
)
ERR
Input short-circuited, or readings at input below the minimum values (e.g. because
thermocouple connected incorrectly).
The 4… 20 mA transmitter is faulty or has no excitation.
SBR
Broken sensor or the input signal is greater than the upper scale value.
EbR
No sensor excitation (strain gage), sensor faulty or not connected.
Ebr
.
Lo
No supply voltage to sensor.
Er
.
rtd
Third wire of Pt100 sensor broken or not connected.
E
.
(AL
.x
Calibration error at input x (x = 1...4).
You can find further information in section: 12.3 "Troubleshooting" on page 140.