background image

13

EN

TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL

overheated, the burner, fan and feeder are disabled.

Аutomatic  Sensor  Check.

 When the temperature 

sensor of the central heating or hot consumption

water is damaged, an alarm is sounded with an 

additional indication shown in the display, e.g.: „

C.H. 

Sensor Damaged

“. 

Blow is disabled and both pumps are activated 

simultaneously, regardless of then temperature. If 

the central heating sensor is damaged, the alarm will 

remain active until the sensor is replaced. If the hot 

consumption water sensor is damaged, pres MENU 

to deactivate the alarm and restore the single (house 

heating) pump mode. To be able to operate the boiler 

in all modes, it is necessary to replace the sensor.

Тemperature  Protection. 

The regulator features 

an additional protection in case the bimetal sensor 

is damaged. After the temperature exceeds 

85°C

the alarm is sounded with the display showing the 

following message:

The current temperature is read from an electronic 

sensor and processed by the thermoregulator. When 

the alarm temperature is exceeded, the fan is shut off 

and both pumps begin to run in order to distribute 

hot consumption water throughout the system.

Anti-Boil Protection.

 This protective function is used 

only with the water heater priority mode. For example, 

when the water heater setpoint temperature is 

Modèle and the boiler temperature rises to 

67°C 

(

5°C

 over the so-called priority temperature), the 

controller shuts off the fan. If the boiler temperature 

reaches 

80°C

, the C.H. pump will be activated. If the 

temperature continues to rise, the alarm will be 

activated at 

85°C

. Such condition may appear when 

the water heater or the pump is damaged or when 

the sensor has been improperly installed. However, 

if the temperature drops, the controller will activate 

the fan at 

66°C

 and it will remain in the duty mode 

maintaining the priority temperature of 

62°C

.

Monitoring the flue gas outlet temperature. This 

sensor constantly monitors the flue gas outlet 

temperature. If the sensor is damaged, disconnected 

from the controller or removed from the flue conduit, 

Flue Gas Sensor Damaged massage will appear on 

the display. This will cause the controller to switch 

to the emergency mode. In such case, only boiler 

temperature is used. The controller is operated using 

only the boiler sensor and the zPID function remains 

active without the flue gas outlet sensor.

Fuse.

 The controller has a network protection WT 

3.15 A

 tube fuse. Higher current ratings may cause 

damage to the controller.

9.13. Controller model ST 81i technical specifications

1.

Supply Voltage

V

230V/50Hz   +/- 10%

2.

Power consumption

W

5

3.

Ambient temperature

°C

10 ÷ 50

4.

Circulation pump outlet load

A

0,5

5.

Fan outlet load

A

0,6

6.

Temperature measurement range

°C

0 ÷ 90

7.

Measurement accuracy

°C

1

8.

Temperature adjustment range

°C

45 ÷ 80

9.

Sensor thermal resistance

°C

- 25 ÷ 100

10.

Fuse inset

А

3,15

10. WARRANTY TERMS

The warranty terms are described in the Service 

booklet included in  the supply.

11. TECHNICAL FEATURES WOOD GASIFYING 

BOILER PyroBurn ALPHA

11.1. General features

Advantages:

- Built-in PID controller with microprocessor which 

monitors and controls the combustion process 

to achieve optimal, efficient and eco- friendly 

operation.

- Flue gas extraction fan

- Flue damper in the upper combustion chamber 

prevents fumigation of the boiler room during 

reloading.

Diagram 9.

- Large and convenient combustion chamber door 

facilitates the loading with wood logs up to 50 cm 

long

Combustion chamber protected by means of 

ceramic lining

- The integrated hook in the upper part of the boiler 

ensures its easy transportation

Summary of Contents for PyroBurn Alpha 18

Page 1: ...ONTAGE undBEDIENUNGSANLEITUNG TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL MANUALE TECNICO ISTRUZIONE di MONTAGGIO e USO model serial Pyrolyse Kessel Serie PyroBurn Alpha Chaudi res pyrolyse s...

Page 2: ...NSPORTATION OF THE BOILER 5 5 DELIVERY OF THE BOILER 5 6 ASSEMBLY OF THE HEATING BOILER 5 6 1 Requirements 5 7 INSTALLATION OF THE HEATING BOILER 6 7 1 Connecting the boiler to a chimney 6 8 BOILER OP...

Page 3: ...3 Customer must undergo boiler operation maintenance training by authorized installer service shop DANGER of fire when burning flammable materials or liquids Flammable materials liquids must not be l...

Page 4: ...r it forms a burnable mixture and is then routed to the nozzle in the combustion chamber In the nozzle the mixture is enriched with secondary air and is self ignited in order to reach the combustion c...

Page 5: ...25 kW 850 1200 120 1470 548 40 kW 850 1200 120 1540 575 5 DELIVERY OF THE BOILER Inspect the integrity of the packaging upon delivery Check whether all components have been delivered to you Boiler sc...

Page 6: ...e heating boiler is equipped with safety heat exchanger cooling circuit It connects to the water system through a thermostatic valve In case of overheating the thermostatic valve feeds in cold water f...

Page 7: ...opens to ignite the boiler In this position the flue gases will be suctioned out through the topmost part of the combustion chamber and then with the help of self igniting additive and saturated kindl...

Page 8: ...m at the drainage outlet Diagram 13 2 Due to accumulation of deposits Condensate and tar formation may reduce the performance and life of the heating boiler The temperature at the boiler inlet must no...

Page 9: ...and the fan is turned off To resume protection remove the black cap on the front panel of the boiler and press the button on the STB thermostat Contact your installer to determine the cause of protec...

Page 10: ...ontrol to manual settings according to parameters entered in the Fitter s Menu to reduce the temperature of the circulation water 9 1 4 Damping If boiler temperature drops by 2 C below the fire up thr...

Page 11: ...temperature drops below the activation temperature minus hysteresis e g 3 C In this case the pump will stop at boiler temperature of 37 C 9 8 Operation mode by selecting one of four operation modes 9...

Page 12: ...emperatures By turning the knob you can change the setpoint temperature After setting the appropriate value confirm it by pressing the encoder knob 9 9 2 H C W Screen This screen displays the current...

Page 13: ...as been improperly installed However if the temperature drops the controller will activate the fan at 66 C and it will remain in the duty mode maintaining the priority temperature of 62 C Monitoring t...

Page 14: ...on chamber 18 kW 1 4 89080031000031 Bottom element of bottom combustion chamber 18 kW 1 5 89080031000038 Side element of bottom combustion chamber 18 kW 2 6 89081282000016 Protective steel plate 4 Dia...

Page 15: ...ction device M Safety heat evacuator inlet outlet E mm R 1070 R 1160 R 1235 Flue F mm 150 970 150 1075 150 1150 J mm 338 382 382 Cleaning opening upper O1 mm 360 120 325 142 455 120 350 140 455 120 35...

Page 16: ...ERUNG 19 5 KESSELLIEFERUNG 19 6 MONTAGE DES HEIZKESSELS 19 6 1 Anforderungen 19 7 HEIZKESSELINSTALLATION 20 7 1 Anschlu des Kessels an einen Schornstein 20 7 2 Anschlu des Sicherheitsw rmeaustauschers...

Page 17: ...sind Wenn die Besch digungen nicht sofort beseitigt werden k nnen darf der Kessel nicht benutzt werden und der Benutzer muss schriftlich bez glich der Besch digung und der ausgehenden davon Gefahr ins...

Page 18: ...nter dem Kesselmantel befindet Am oberen Teil des Kessels ist ein PID Kontroller gestellt Konstruktion Der Kesselk rper ist aus hochwertigem Kesselstahl gebaut 6 mm stark f r die Brennkammer und 4 mm...

Page 19: ...latz empfohlen Bei Transportierung und Montage m ssen abh ngig vom Gewicht Sicherheitsmittel in bereinstimmung der Richtlinie 2006 42 benutzt werden Bei der Transportierung von Gegenst nden mit Gewich...

Page 20: ...s 9 M Mindestens 9 M Mindestens 8 M Mindestens 8 M 40 kW 180 mm 200 mm 220mm Mindestens 11 M Mindestens 10 M Mindestens 10 M i Die angegebene in diesem Schema Daten sind durchschnittlich Die Zugkraft...

Page 21: ...n zuerst die Normalma H lzer wenigstens 3 Schichten anzuordnen und darauf alle kleine und unf rmige Holzschnitte Ordnen Sie das Holz dicht ohne Luftzwischenbereiche Merken Sie die Regel die kleinste u...

Page 22: ...mlaufpumpe muss die Kesselarbeit von einem Thermostat geregelt sein damit die vorgeschriebene Nominaltemperatur des zur ckflie enden Wassers erreicht wird Der Kessel arbeitet umweltfreundlich bei der...

Page 23: ...ft abh ngig von dem Holzkaloriengehalt 3 Erhebliche Ablagerung von Ru flocken und Katranen auf dem Ventilator st ren seine Normalarbeit 3 Wenden Sie sich an einem autorosierten Service f r die Ventila...

Page 24: ...e Zentralheizung Pumpe f r heizes Gebrauchswasser Handsteuerung Hauptdruckknopf Betrieb Bereitschaft EXIT Ausgang Best tigen Sie Mit dem Hauptdruckknopf kann man alle Parameter ver ndern Durch Drehung...

Page 25: ...eingeben dr cken Sie die Taste um zu best tigen Im Kapitel Monitor sind die Methoden f r Ver nderung des Hauptansichts vom Monitor beschrieben 9 4 Anz ndung Fire up Nach Entz ndung m ssen Sie den auto...

Page 26: ...g Der Kessel soll montierte R ckschlagventile haben an der Pumpe f r Zentralheizung und an der Pumpe f r Gebrauchswasser um die Mischung des Wassers von den beiden Systemen zu vermeiden 9 8 3 Parallel...

Page 27: ...erte Mitteilung C H Temperature Too High zu hohe Temperatur f r das Heizsystem warten Sie bis die Temperatur unter dem kritischen Punkt f llt W rmeschutz Der Kessel ist mit einem zus tzlichen bi metal...

Page 28: ...ng Der Regler ist mit Rohrschutzvorrichtung tube fuse WT 3 15 A H here Werte k nnen zu Kontrollerbesch digung f hren 10 13 Technische Charakteristiken des Kontrollers Modell ST 81 i 1 Arbeitsspannung...

Page 29: ...Brennkammer 18 kW 1 5 89080031000038 Seitenteil unterer Brennammer 18 kW 2 6 89081282000016 Sicherungsstahlplatte 4 Schema 12 Elemente der Brennkammer von 25kW 40kW Tabelle 8 1 Nr Kode PB Alpha 25 kW...

Page 30: ...ung M P P P Eing Ausg Sicherheitsw rmeaustauscher E mm R 1070 R 1160 R 1235 Schornsteinrohr F mm J mm 150 970 338 150 1075 382 150 1150 382 Revisions ffnung im oberen Teil im unnteren Teil O1 mm O2 mm...

Page 31: ...E 34 6 INSTALLATION DE LA CHAUDI RE 34 6 1 Exigences 35 7 INSTALLATION DE LA CHAUDI RE 35 7 1 Raccordement de la chaudi re la chemin e 35 7 2 Raccordement de l changeur de chaleur de s curit 35 8 FONC...

Page 32: ...L installateur autoris service est oblig de faire la formation l utilisateur pour le fonctionnement et le nettoyage de la chaudi re DANGER d intoxication de touffement L air insuffisant dans la chauff...

Page 33: ...chambre de combustion br lant les gaz de bois avec rev tement des l ments en c ramiques En face de la partie sup rieure de la chaudi re se trouve la porte pour charger la chambre sup rieure avec bois...

Page 34: ...Puissance calorifique du bois le plus r pandu Esp ce de bois nergie contenue dans 1 kg kcal kJoule kWh pic a 3900 16250 4 5 Pin 3800 15800 4 4 Bouleau 3750 15500 4 3 Ch ne 3600 15100 4 2 H tre 3450 14...

Page 35: ...r e Le diam tre de la chemin e ne doit pas tre inf rieur que la sortie de la chaudi re Le conduit de fum es doit tre raccord l orifice de la chemin e En termes de propri t s m caniques le conduit de f...

Page 36: ...avec des espaces d air minimales entre les morceaux de bois c est une condition importante pour le bon fonctionnement de la combustion de pyrolyse Lors de rangement du bois dans la chambre de combust...

Page 37: ...e quand son niveau atteint 1 3 du volume de la chambre Sch ma 8 La cendre non nettoy agit sur le fonctionnement de la chaudi re Sch ma 8 8 3 Recommandations importantes pour le fonctionnement durable...

Page 38: ...haudi re Ceci est r alis par un centre de service autoris La chaudi re ne peut pas tre r gl e Il n a pas de combustion pyrolyse 1 Les portes de la chaudi re ne se ferment pas bien 1 V rifiez la corde...

Page 39: ...le conduit de fum e Explication des boutons Ventilateur Pompe Chauffage Central C C Pompe Eau chaude sanitaire ECS Commande manuel Bouton principal Mode En veille EXIT Sortie Confirmer Tous les param...

Page 40: ...t en mode En veille Si la temp rature d allumage atteint son seuil l affichage Allumage sur l cran sera remplac par Ventilateur partir de ce moment l option sera utilis e pour activ d sactiv du ventil...

Reviews: