3

EN

TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL

1. EXPLANATION OF SYMBOLS AND SAFETY 

INSTRUCTIONS

1.1. Explanation of symbols

CAUTION!  -

 Important recommendation or 

warning concerning safety conditions during 

installation and operation of the heating 

boiler

DANGER! - 

fault or improper use may cause 

injury or be hazardous to the life of humans 

or animals.

FIRE HAZARD! - 

fault or improper installation 

and operation may cause fire.

INFORMATION  - 

Important information on 

the proper operation of the product.

1.2. Requirements to boiler installation room

This manual contains important information for the 

safe and correct installation, start-up and trouble-

free service and maintenance of the heating boiler.

The heating boiler can be used for heating rooms 

only in the manner described in this manual.

Take note of the boiler type information indicated on 

the factory sticker and the technical data provided in 

chapter 11.3 in order to ensure proper operation of 

the product.

1.2.1. Instructions to boiler installer

During installation and operation, the country-

specific requirements and regulations must be 

observed:

• local  building  regulations  on  the  installation, 

air supply and exhaust gas extraction as well as 

chimney connection.

• regulations and norms concerning the fitting of the 

heating installation with safety devices.

i

Use only original BURNiT parts

DANGER of intoxication, suffocation.

Inadequate inflow of fresh air in the boiler 

room  may  result  in  dangerous  leak  of 

exhaust gases during boiler operation.

Make sure the air inlets and exhaust gas 

outlets are not clogged or closed.

-  If faults are not remedied immediately, the 

boiler must not be operated, and the user 

must be provided with written instructions 

on the fault and the hazard it entails.

*

It is mandatory to assure a backup power 

generator  of  corresponding  rated  power! 

(see 11.3)

*

Customer must undergo boiler operation/

maintenance  training  by  authorized 

installer/service shop.

!

DANGER  of  fire  when  burning  flammable 

materials or liquids.

- Flammable materials/liquids must not be 

left in immediate proximity of the heating 

boiler. 

-  Indicate to the installation user the allowed 

minimum clearances from surrounding 

objects.

1.2.2. 

Instructions to installation user

$

DANGER of intoxication or explosion

Toxic  gases  may  be  discharged  when 

burning waste, plastics, liquids.

- Use only the fuels indicated in this manual.

- In case of danger of explosion, ignition or 

discharge of exhaust gases in the room, 

stop the heating boiler from operation.

*

CAUTION!  Danger  of  injury  /  damage  of 

installation due to incompetent operation.

- The heating boiler must be serviced only 

by persons familiar with the operation 

manual.

- As a user, you are only allowed to start the 

boiler up, adjust the temperature of the 

boiler, shut the boiler down and clean it.

- Unattended children must not be allowed 

to access a room housing a running boiler.

*

Customer must undergo boiler operation/

maintenance  training  by  authorized 

installer/service shop.

*

It is mandatory to assure a backup power 

generator  of  corresponding  rated  power! 

(see 11.3)

Safety rules for user operation:

Operate the heating boiler at a maximum 

temperature of 

85°C

, and to that end you must 

regularly inspect the boiler room.

- Do not use flammable liquids to ignite the fire or 

increase boiler’s output .

- Collect the ash in a fire-proof container with a lid.

Clean the heating boiler surface using non-

flammable agents only.

- Do not place flammable objects onto the heating 

boiler or in its proximity. (see diagram 1 for the 

minimum clearances)

- Do not store flammable materials in the boiler room.

1.2.3.  Minimum  clearances  for  installation  and 

combustibility of building materials

The applicable minimum clearances in your country 

may differ from the ones specified bellow. Please, 

consult your installer.

The minimum distance from the heating boiler or 

exhaust gas pipe to objects or walls must be at least 

200 mm.

Summary of Contents for PyroBurn Alpha 18

Page 1: ...ONTAGE undBEDIENUNGSANLEITUNG TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL MANUALE TECNICO ISTRUZIONE di MONTAGGIO e USO model serial Pyrolyse Kessel Serie PyroBurn Alpha Chaudi res pyrolyse s...

Page 2: ...NSPORTATION OF THE BOILER 5 5 DELIVERY OF THE BOILER 5 6 ASSEMBLY OF THE HEATING BOILER 5 6 1 Requirements 5 7 INSTALLATION OF THE HEATING BOILER 6 7 1 Connecting the boiler to a chimney 6 8 BOILER OP...

Page 3: ...3 Customer must undergo boiler operation maintenance training by authorized installer service shop DANGER of fire when burning flammable materials or liquids Flammable materials liquids must not be l...

Page 4: ...r it forms a burnable mixture and is then routed to the nozzle in the combustion chamber In the nozzle the mixture is enriched with secondary air and is self ignited in order to reach the combustion c...

Page 5: ...25 kW 850 1200 120 1470 548 40 kW 850 1200 120 1540 575 5 DELIVERY OF THE BOILER Inspect the integrity of the packaging upon delivery Check whether all components have been delivered to you Boiler sc...

Page 6: ...e heating boiler is equipped with safety heat exchanger cooling circuit It connects to the water system through a thermostatic valve In case of overheating the thermostatic valve feeds in cold water f...

Page 7: ...opens to ignite the boiler In this position the flue gases will be suctioned out through the topmost part of the combustion chamber and then with the help of self igniting additive and saturated kindl...

Page 8: ...m at the drainage outlet Diagram 13 2 Due to accumulation of deposits Condensate and tar formation may reduce the performance and life of the heating boiler The temperature at the boiler inlet must no...

Page 9: ...and the fan is turned off To resume protection remove the black cap on the front panel of the boiler and press the button on the STB thermostat Contact your installer to determine the cause of protec...

Page 10: ...ontrol to manual settings according to parameters entered in the Fitter s Menu to reduce the temperature of the circulation water 9 1 4 Damping If boiler temperature drops by 2 C below the fire up thr...

Page 11: ...temperature drops below the activation temperature minus hysteresis e g 3 C In this case the pump will stop at boiler temperature of 37 C 9 8 Operation mode by selecting one of four operation modes 9...

Page 12: ...emperatures By turning the knob you can change the setpoint temperature After setting the appropriate value confirm it by pressing the encoder knob 9 9 2 H C W Screen This screen displays the current...

Page 13: ...as been improperly installed However if the temperature drops the controller will activate the fan at 66 C and it will remain in the duty mode maintaining the priority temperature of 62 C Monitoring t...

Page 14: ...on chamber 18 kW 1 4 89080031000031 Bottom element of bottom combustion chamber 18 kW 1 5 89080031000038 Side element of bottom combustion chamber 18 kW 2 6 89081282000016 Protective steel plate 4 Dia...

Page 15: ...ction device M Safety heat evacuator inlet outlet E mm R 1070 R 1160 R 1235 Flue F mm 150 970 150 1075 150 1150 J mm 338 382 382 Cleaning opening upper O1 mm 360 120 325 142 455 120 350 140 455 120 35...

Page 16: ...ERUNG 19 5 KESSELLIEFERUNG 19 6 MONTAGE DES HEIZKESSELS 19 6 1 Anforderungen 19 7 HEIZKESSELINSTALLATION 20 7 1 Anschlu des Kessels an einen Schornstein 20 7 2 Anschlu des Sicherheitsw rmeaustauschers...

Page 17: ...sind Wenn die Besch digungen nicht sofort beseitigt werden k nnen darf der Kessel nicht benutzt werden und der Benutzer muss schriftlich bez glich der Besch digung und der ausgehenden davon Gefahr ins...

Page 18: ...nter dem Kesselmantel befindet Am oberen Teil des Kessels ist ein PID Kontroller gestellt Konstruktion Der Kesselk rper ist aus hochwertigem Kesselstahl gebaut 6 mm stark f r die Brennkammer und 4 mm...

Page 19: ...latz empfohlen Bei Transportierung und Montage m ssen abh ngig vom Gewicht Sicherheitsmittel in bereinstimmung der Richtlinie 2006 42 benutzt werden Bei der Transportierung von Gegenst nden mit Gewich...

Page 20: ...s 9 M Mindestens 9 M Mindestens 8 M Mindestens 8 M 40 kW 180 mm 200 mm 220mm Mindestens 11 M Mindestens 10 M Mindestens 10 M i Die angegebene in diesem Schema Daten sind durchschnittlich Die Zugkraft...

Page 21: ...n zuerst die Normalma H lzer wenigstens 3 Schichten anzuordnen und darauf alle kleine und unf rmige Holzschnitte Ordnen Sie das Holz dicht ohne Luftzwischenbereiche Merken Sie die Regel die kleinste u...

Page 22: ...mlaufpumpe muss die Kesselarbeit von einem Thermostat geregelt sein damit die vorgeschriebene Nominaltemperatur des zur ckflie enden Wassers erreicht wird Der Kessel arbeitet umweltfreundlich bei der...

Page 23: ...ft abh ngig von dem Holzkaloriengehalt 3 Erhebliche Ablagerung von Ru flocken und Katranen auf dem Ventilator st ren seine Normalarbeit 3 Wenden Sie sich an einem autorosierten Service f r die Ventila...

Page 24: ...e Zentralheizung Pumpe f r heizes Gebrauchswasser Handsteuerung Hauptdruckknopf Betrieb Bereitschaft EXIT Ausgang Best tigen Sie Mit dem Hauptdruckknopf kann man alle Parameter ver ndern Durch Drehung...

Page 25: ...eingeben dr cken Sie die Taste um zu best tigen Im Kapitel Monitor sind die Methoden f r Ver nderung des Hauptansichts vom Monitor beschrieben 9 4 Anz ndung Fire up Nach Entz ndung m ssen Sie den auto...

Page 26: ...g Der Kessel soll montierte R ckschlagventile haben an der Pumpe f r Zentralheizung und an der Pumpe f r Gebrauchswasser um die Mischung des Wassers von den beiden Systemen zu vermeiden 9 8 3 Parallel...

Page 27: ...erte Mitteilung C H Temperature Too High zu hohe Temperatur f r das Heizsystem warten Sie bis die Temperatur unter dem kritischen Punkt f llt W rmeschutz Der Kessel ist mit einem zus tzlichen bi metal...

Page 28: ...ng Der Regler ist mit Rohrschutzvorrichtung tube fuse WT 3 15 A H here Werte k nnen zu Kontrollerbesch digung f hren 10 13 Technische Charakteristiken des Kontrollers Modell ST 81 i 1 Arbeitsspannung...

Page 29: ...Brennkammer 18 kW 1 5 89080031000038 Seitenteil unterer Brennammer 18 kW 2 6 89081282000016 Sicherungsstahlplatte 4 Schema 12 Elemente der Brennkammer von 25kW 40kW Tabelle 8 1 Nr Kode PB Alpha 25 kW...

Page 30: ...ung M P P P Eing Ausg Sicherheitsw rmeaustauscher E mm R 1070 R 1160 R 1235 Schornsteinrohr F mm J mm 150 970 338 150 1075 382 150 1150 382 Revisions ffnung im oberen Teil im unnteren Teil O1 mm O2 mm...

Page 31: ...E 34 6 INSTALLATION DE LA CHAUDI RE 34 6 1 Exigences 35 7 INSTALLATION DE LA CHAUDI RE 35 7 1 Raccordement de la chaudi re la chemin e 35 7 2 Raccordement de l changeur de chaleur de s curit 35 8 FONC...

Page 32: ...L installateur autoris service est oblig de faire la formation l utilisateur pour le fonctionnement et le nettoyage de la chaudi re DANGER d intoxication de touffement L air insuffisant dans la chauff...

Page 33: ...chambre de combustion br lant les gaz de bois avec rev tement des l ments en c ramiques En face de la partie sup rieure de la chaudi re se trouve la porte pour charger la chambre sup rieure avec bois...

Page 34: ...Puissance calorifique du bois le plus r pandu Esp ce de bois nergie contenue dans 1 kg kcal kJoule kWh pic a 3900 16250 4 5 Pin 3800 15800 4 4 Bouleau 3750 15500 4 3 Ch ne 3600 15100 4 2 H tre 3450 14...

Page 35: ...r e Le diam tre de la chemin e ne doit pas tre inf rieur que la sortie de la chaudi re Le conduit de fum es doit tre raccord l orifice de la chemin e En termes de propri t s m caniques le conduit de f...

Page 36: ...avec des espaces d air minimales entre les morceaux de bois c est une condition importante pour le bon fonctionnement de la combustion de pyrolyse Lors de rangement du bois dans la chambre de combust...

Page 37: ...e quand son niveau atteint 1 3 du volume de la chambre Sch ma 8 La cendre non nettoy agit sur le fonctionnement de la chaudi re Sch ma 8 8 3 Recommandations importantes pour le fonctionnement durable...

Page 38: ...haudi re Ceci est r alis par un centre de service autoris La chaudi re ne peut pas tre r gl e Il n a pas de combustion pyrolyse 1 Les portes de la chaudi re ne se ferment pas bien 1 V rifiez la corde...

Page 39: ...le conduit de fum e Explication des boutons Ventilateur Pompe Chauffage Central C C Pompe Eau chaude sanitaire ECS Commande manuel Bouton principal Mode En veille EXIT Sortie Confirmer Tous les param...

Page 40: ...t en mode En veille Si la temp rature d allumage atteint son seuil l affichage Allumage sur l cran sera remplac par Ventilateur partir de ce moment l option sera utilis e pour activ d sactiv du ventil...

Reviews: