41
Setting and operation
Type 8746 Profibus, 8746 Analogue
10.2.2 flush mode (Mfc Profibus)
NOTICE
If the control valve is fully open, then the internal product temper
-
ature increases. And if the internal product temperature increases,
then the product can be damaged.
•
Do not let the control valve fully open for more than
10 minutes.
To open the control valve completely, send one of the following
commands to the product:
•
an acyclic command
•
a cyclic command with the double nominal flow rate
10.3 Tools for doing settings
The MassFlowCommunicator is another PC software
that is not compatible with the product. You cannot use
the MassFlowCommunicator software to configure or
operate the product.
Settings can be done with the Type 8920 Bürkert Communicator
software.
→
To connect the product to the Bürkert Communicator
software, refer to chpt. 10.4
→
For general information about the Bürkert Communicator
software, refer to the Type 8920 Operating Instructions.
10.4 connect the product to the Bürkert
communicator software
To do the settings with the Type 8920 Bürkert Communicator
software, do the following steps:
→
Buy the USB-büS-interface set with article number 00772551
from Bürkert.
→
Download the latest version of the Type 8920 Bürkert Com
-
→
Install the Bürkert Communicator software on a PC. During
installation, the büS stick must not be inserted at the PC.
→
Assemble the parts of the USB-büS-interface set. Refer to
.
Fig. 24:
Assembled parts of the USB-büS-interface set with article
number 00772551
→
Set the termination-resistance switch of the büS stick to ON.
→
Insert the büS stick into a USB port of the PC.
English