39
Commissioning
Type 8746 Profibus, 8746 Analogue
9
coMMiSSioNiNG
9.1
Safety instructions
WARNING
risk of injury from improper commissioning and operation.
Improper commissioning and operation can lead to injuries and
damage to the product and its environment.
▶
Before commissioning, make sure that the operating person
-
nel are familiar with, and fully understand the content of the
Operating Instructions.
▶
Observe the safety information and the intended use.
▶
Only properly trained personnel may commission the instal
-
lation and the product.
▶
Only properly trained personnel may do the settings with the
help of the Bürkert Communicator software.
9.2
commissioning steps
1.
Pressurise the pipes with operating fluid
2.
Flush the pipes with operating fluid at the calibration
pressure.
3.
Vent the pipes completely.
4.
Energise the product.
If product-specific data is stored on the inserted memory
card, then the product adopts the data. To get a list of the stored
data at product delivery, refer to the Help for the Initiation file that
can be downloaded from
If the inserted memory card is empty, then the product loads
its own data on the memory card. Possible problems related to
the memory card are given in chpt.
and chpt.
NOTICE
If the memory card is defective or lost, then buy a new memory
card from your Bürkert sales office.
5.
If the product is an MFC, and the operating fluid is not the
calibration fluid or the pressure conditions have changed,
then run the Autotune function. See chpt. 10.8 Optimise the
closed-loop control parameters (MFC)
The product operates normally.