SDT16 Family Installation and Configuration Guide
82
Chapter 3. Configuration
2.
Type the unit address assigned to the input device in the
Unit Address
field. Valid entries
are any number from 1 to 255.
3.
Type the register address of the input device in the
Register Address
field. Valid entries
include any address from 1 to 65,535.
4.
Choose a scale value by clicking the up or down arrow buttons located next to the
Scale
field. The up arrow moves the decimal to the left and the down arrow moves the decimal
to the right.
The scale value you select displays below the field. It shows an example of how the selected
scale value applies to the register reading. The process the Bullhorn unit uses to scale a raw
register readings is:
•
Divide the raw reading by the scale value.
•
Select the first six digits to the left of the decimal point for a 6-digit register or the
first twelve digits to the left of the decimal point if working with a
Double Register
(12-digit register).
•
If necessary, add leading zeroes to the left of the number to produce either a 6-digit
scaled reading or a 12-digit scaled reading if working with a
Double Register
.
N
OTE
:
If you are working with a 6 or 12-digit register and the scaled reading is larger
than 6 or 12 digits respectively, the Bullhorn unit reports a register reading of
999999
.
The Bullhorn website displays scaled readings according to the
multiplier
value you
select on the website.
5.
Click the arrow in the
Data Type
list box and select an option from the list that identifies
the register data type.
If needed, refer to the technical specifications for the input device or contact the
manufacturer to help determine the correct data type. An incorrect data type causes the
Bullhorn unit to report an incorrect register reading.
N
OTE
:
The options in the
Packet Options
group box are unavailable for selection.
6.
If you are working with an odd-numbered
Channel
window and you want to map a 12-digit
register, click the
Double Register
option box.
7.
Click
Save + Next Register
to save settings and display the next
Channel Number
configuration window. If you do not want to configure another channel, click
Save
to save
settings and close the configuration window.
8.
When you finish configuring all channels, continue with
Save Configuration Settings in the Event
N
OTE
:
If you need to unmap a register, refer to
Summary of Contents for SDT16 Family
Page 1: ...Installation and Configuration Guide SDT16 Family Satellite and Digital Cellular Units...
Page 2: ......
Page 8: ...SDT16 Family Installation and Configuration Guide viii Contents...
Page 64: ...SDT16 Family Installation and Configuration Guide 54 Chapter 2 Installation...
Page 102: ...SDT16 Family Installation and Configuration Guide 92 Chapter 4 Maintenance...
Page 104: ...SDT16 Family Installation and Configuration Guide 94 Appendix A Regulatory Notices...
Page 109: ......