2
Installation
12
Installation and maintenance instructions Logano GE315 • Issue 02/2006
We reserve the right to make any changes due to technical modifications.
Fig. 7
Burr removal
Fig. 8
Preparation of packing grooves and hubs
Fig. 9
Hammering the nipples home
2
1
3
1
2
2.4.2
Fitting the boiler sections (unassembled)
Prior to fitting the front and rear sections, remove the
nuts and washers from the bolts on the boiler section
hubs.
z
Position the rear section and secure against falling.
z
Remove possible burrs from the hub using a file
(Fig. 7).
z
Clean the packing groove (Fig. 8,
) where
required using a wire brush and cloth.
z
Clean the hub sealing faces (Fig. 8,
Item 1 & 2
) with
a cloth soaked in white spirit.
z
Coat the hub sealing faces evenly with the orange
sealing compound (Marked as LEINOMENNIGE).
During the next step, the nipples are prepared for the
closing up of the boiler sections.
z
Clean nipples with a cloth soaked in white spirit and
coat half the surface with the orange sealing
compound.
z
Fit the nipples straight into the upper (size 2,119/50)
and lower (size 0, 57/50) hub of the rear section and
hammer home securely with alternate heavy blows.
Afterwards, the upper nipple (Fig. 9,
) and the
lower nipple (Fig. 9,
Item 2
) should protrude approx.
28 mm from the respective hub.
z
Remove any burrs which might have been created
with a file. Finish coating the outer surface of the
nipple with orange sealing compound.