Fault messages
Display
Display after
pressing the
service button
Meaning
Trouble-
shooting
flow diagram
2
Water flow
C
Safety sensor exceeds 100 °C
P
Excessive temperature increase at safety sensor
3
Air volume flow
C
Bad plug-in connection at cable loom, or damaged wiring
4
Temperatures
A
Feed sensor above 100 °C
C
F2 fuse malfunction, or exhaust-gas sensor tripped
F
Safety sensor exceeds 100 °C
H
Dripping tap
L
Short circuit in safety sensor
P
Safety sensor, loose contact or defective
U
Short circuit in feed sensor
y
Feed sensor, loose contact or defective
5
Communication
C
600 series has switched off after disconnection of diagnosis plug
6
Flame monitoring
A
F1 fuse defective, or no ionisation message after ignition
C
Ionisation message, but no flame
H
Flame dies out after gas valve is opened
L
Flame goes out during warm-up phase