Troubleshooting
3
Subject to modifications resulting from technical improvements!
Buderus Ltd. • http://www.buderus-domestic.co.uk
Servicing manual for wall-mounted condensing gas boiler 600 Series 11S/19S/24S/24C • Issued 02/2006
27
Fig. 24
Continuation of fault warning message 6A: F1 fuse defective, or no ionisation message after ignition
Replace fan unit
No
Plug OK?
Fit the casing
"reset"
600 Series
11S / 19S / 24S / 24C
OK
23
Check that the fan-unit connection
plug is correctly inserted
Insert plug correctly
Yes