Fig. 17
Fault warning message 4P: Safety sensor, loose contact or defect
Flashing
4
Safety sensor, loose contact
or defect
Yes
Replace cable (page 55)
Remove the casing (page 48)
Check safety sensor (page 55)
Replace safety sensor (page 55)
A
No
No
No
Yes
Yes
P
"reset"
New fault warning
message
4P
?
Check wiring to safety sensor for loose
contacts (page 55)
Wiring OK?
Safety sensor
OK?
Fit the casing
"reset"
600 Series
11S / 19S / 24S / 24C
OK