Troubleshooting
3
Subject to modifications resulting from technical improvements!
Buderus Ltd. • http://www.buderus-domestic.co.uk
Servicing manual for wall-mounted condensing gas boiler 600 Series 11S/19S/24S/24C • Issued 02/2006
15
Fig. 12
Fault warning message 4C: F2 fuse malfunction, or exhaust-gas sensor tripped
Flashing
4
F2 fuse malfunction, or exhaust-gas
sensor tripped
Yes
Connect lead correctly
Remove the casing (page 48)
Check wiring connection of UBA
Fuse (1.25 AT) should be
replaced
18
No
No
No
Yes
Yes
C
"reset"
New fault
warning message
4C
?
Check miniature fuse F2 (page 53)
Miniature fuse F2 OK?
Wiring connection
OK?
Check exhaust-gas sensor
No
Replace exhaust-gas sensor
19
20
Yes
Exhaust-gas
sensor OK?