background image

4

Table 1 – Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (in.)

Information is Specific to 286A and 288A Models

UNIT SIZE

LIQUID

RATED VAPOR*

Connection

Diameter

Tube

Diameter

Connection

Diameter

Tube

Diameter

286A024

3/8

3/8

5/8

5/8

286A036

3/8

3/8

3/4

3/4

286A048

3/8

3/8

7/8

7/8

286A060

3/8

3/8

7/8

1--1/8

288A024

3/8

3/8

3/4

3/4

288A036

3/8

3/8

3/4

3/4

288A048

3/8

3/8

7/8

7/8

288A060

3/8

3/8

7/8

1--1/8

* Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance data when using different size and length linesets.

Notes

:

1. Do not apply capillary tube or the fixed orifice indoor coils to these units.

2 For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 20 ft. (6.10 m) vertical differential (250 ft./76.2 m Total Equivalent Length),

refer to the Residential Piping and Long Line Guideline for Air Conditioners and Heat Pumps using Puron

®

Refrigerant.

Table 2 – Accessory Usage

ACCESSORY

REQUIRED FOR LOW---AMBIENT

COOLING APPLICATIONS

(Below 55

°

F/12.8

_

C)

REQUIRED FOR LONG LINE

APPLICATIONS*

REQUIRED FOR SEA COAST

APPLICATIONS

(Within 2 miles/3.22 km)

Crankcase Heater

Standard

Standard

Standard

Evaporator Freeze Protection

Standard with Evolution

t

Control

(Low Ambient not allowed with

non---communicating thermostat)

No

No

Winter Start Control

Standard with Evolution Control

(Low Ambient not allowed with non---

communicating thermostat)

No

No

Compressor Start Assist Capacitor

and Relay

}

Standard on 286A models.

Not required for 288A

Standard on 286A models

.

Not required for 288A

Standard on 286A models

Not required for 288A

Low---Ambient Control

Standard with Evolution Control

(Low ambient not allowed with non---

communicating thermostat)

No

No

Support Feet

Recommended

No

Recommended

Liquid---Line Solenoid Valve

No

Yes

No

Puron Refrigerant Balance Port

Hard---Shut Off TXV

Yes

{

Yes

{

Yes

{

* For tubing set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 20 ft. (6.10 m) vertical differential (total equivalent length), refer to the

Residential Piping and Long Line Guideline for Air Conditioners and Heat Pumps using Puron

®

Refrigerant.

{

Required on all indoor units. Standard on all new Puron refrigerant fan coils and furnace coils.

}

Information is specific to 286A and 288A models.

the environmentally sound refrigerant

REGISTERED

ISO 9001:2000

This product has been designed and manufactured to

meet Energy Star

®

criteria for energy efficiency when

matched with appropriate coil components. However,

proper refrigerant charge and proper air flow are critical

to achieve rated capacity and efficiency. Installation of

this product should follow all manufacturing refrigerant

charging and air flow instructions.

Failure to confirm

proper charge and air flow may reduce energy

efficiency and shorten equipment life.

Ready for use in a Hybrid Heat

r

Duel Fuel system.

286A

/288A

Summary of Contents for Evolutiont 286A

Page 1: ...rmation This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could resul...

Page 2: ...nt tubing sets metering device and filter drier listed in presale literature There can be no deviation Consult the Service Manual Air Conditioners and Heat Pumps Using Puron Refrigerant to obtain required unit changes for specific applications and for R 22 retrofit Check Equipment and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit Inspect Equipment File cl...

Page 3: ...outdoor unit Make Piping Connections WARNING PERSONAL INJURY AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal injury or death Relieve pressure and recover all refrigerant before system repair or final unit disposal Use all service ports and open all flow control devices including solenoid valves CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in e...

Page 4: ...rd with Evolution Control Low Ambient not allowed with non communicating thermostat No No Compressor Start Assist Capacitor and Relay Standard on 286A models Not required for 288A Standard on 286A models Not required for 288A Standard on 286A models Not required for 288A Low Ambient Control Standard with Evolution Control Low ambient not allowed with non communicating thermostat No No Support Feet...

Page 5: ...rant Tubing and Indoor Coil CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Never use the system compressor as a vacuum pump Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns The alternate triple evacuation method may be used See Service Manual for triple evacuation method Alw...

Page 6: ...nstructions packaged with kits or accessories when installing Make Airflow Selections Airflow Setup for Evolution Control Furnace of FE Fan coil communicating When using an Evolution User Interface airflow is automatically selected based on equipment size See User Interface Installation Instructions for available adjustments Airflow Selection for Variable Speed Furnaces for Non Communicating non E...

Page 7: ...mand high stage cooling is energized by the second stage of indoor thermostat or User Interface After second stage is satisfied the unit returns to low stage operation until first stage is satisfied or until second stage is required again When both first stage and second stage cooling are satisfied the compressor will shut off The reversing valve will remain energized until the control board power...

Page 8: ...put for both high and low stage equals the value for low stage opera tion below 55_F 12 8_C Time Delays The unit time delays include S Five minute time delay to start cooling or heating operation when there is a call from the thermostat or user interface To bypass this feature momentarily short and release Forced Defrost pins S Five minute compressor re cycle delay on return from a brown out condi...

Page 9: ...odels the PWM output for both high and low stage equals the value for low stage operation below 55_F 12 8_C Defrost This control offers 5 possible defrost interval times 30 60 90 120 minutes or AUTO These are selected by dip switches on the unit control board or by the Evolution Control User Interface The Evolution Control selection overrides the control board dip switch settings AUTO defrost adju...

Page 10: ...e solenoid should be installed near the outdoor unit with the arrow facing the outdoor unit This is the direction of flow control See application manual for long line application details Accessory Liquid Solenoid with Evolution Communicating Control When using the Evolution Control the liquid line solenoid output is provided at the Y1 connection Connect the solenoid as shown in the wiring label di...

Page 11: ...and serial information If the factory control board fails the model plug must be transferred from the original board to the replacement board for the unit to operate NOTE The model plug takes priority over factory model information input at the factory If the model plug is removed after initial power up the unit will operate according to the last valid model plug installed and flash the appropriat...

Page 12: ...t sensed when the compressor should be starting the appropriate contactor may be stuck open or there is a wiring error The control will flash the appropriate fault code Check the contactor and control box wiring 286A Models Only Compressor Start Detection on Models with Bristol Compressors Only In low stage if the specified start voltage at VR terminal is not achieved the start relay is de energiz...

Page 13: ... performed during low ambient cooling or defrost operation Failed Thermistor Default Operation Factory defaults have been provided in the event of failure of outdoor air thermistor OAT and or outdoor coil thermistor OCT If the OAT sensor should fail low ambient cooling will not be allowed and the one minute outdoor fan off delay will not occur Defrost will be initiated based on coil temperature an...

Page 14: ...relay and capacitor held in circuit too long if installed High Stage Thermal Cutout 72 Compressor operation detected then disappears while high stage demand exists Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long if installed Contactor Shorted 73 Compressor voltage sensed when no demand for compressor operation exists Contactor may be stuc...

Page 15: ... W1 W2 Heat Cool Stage 1 Y1 W2 Y1 Heat Cool Stage 2 Y Y2 Y Y2 Y Y2 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DHUM 24VAC Common C COM C Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor Variable Speed Furnace Thermidistat 2 Stage Heat Pump Indicates connection may not be...

Page 16: ...e hoses with 700 psig service pressure rating 12 Leak detectors should be designed to detect HFC refrigerant 13 Puron refrigerant as with other HFCs is only compatible with POE oils 14 Vacuum pumps will not remove moisture from oil 15 Do not use liquid line filter driers with rated working pressures less than 600 psig 16 Do not leave Puron refrigerant suction line filter driers in line longer than...

Reviews: