background image

7

Start--Up

CAUTION

!

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this caution may result in minor personal

injury, equipment damage or improper operation.
Observe the following:
1. Do not overcharge system with refrigerant.
2. Do not operate unit in a vacuum or at negative pressure.
3. Do not disable low pressure switch
4. Dome temperatures may be hot.

CAUTION

!

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal injury.
Wear safety glasses, protective clothing, and gloves when

handling refrigerant.

CAUTION

!

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmental

damage.
Federal regulations require that you do not vent

refrigerant to the atmosphere. Recover during system

repair or final unit disposal.

Follow these steps to properly start up the system:

1. After system is evacuated, fully back seat (open) liquid and

vapor service valves.

2. Unit is shipped with valve stem(s) front seated (closed) and

caps installed. Replace stem caps after system is opened to

refrigerant flow (back seated). Replace caps finger--tight and
tighten with wrench an additional 1/12 turn.

3. Close electrical disconnects to energize system.
4. Set room thermostat or User Interface at desired temperat-

ure. Be sure set point is below indoor ambient temperature

and is set low enough to energize desired stage.

5. Set room thermostat or User Interface to COOL and fan

control to ON or AUTO mode, as desired. Operate unit for
15 minutes. Check system refrigerant charge.

NOTE

: Non--communicating (non--Evolution) Bryant thermostats

are equipped with a 15--minute staging timer. This timer prevents
the two--stage system from operating at high stage until unit has
been operating in low stage for 15 minutes, unless there is at least a

±

5

°

F (

±

2.8

°

C) difference between room temperature and thermostat

set point. To force high stage (after a minimum of 2 minutes in low
stage), adjust the set point at least

±

5

°

F (

±

2.8

°

C) below room

ambient.

6. Set room thermostat or User Interface to HEAT or COOL

and fan control to AUTO or ON, as desired. Wait for appro-

priate time delay(s). Operate unit for 15 minutes. Check re-
frigerant charge.

System Functions and Sequence of Operation

The outdoor unit control system has special functions. The
following is an overview of the two--stage control functions:

Cooling and Heating Operation

The 286A and 288A (containing circuit board HK38EA015 or

newer) models utilize either a standard indoor thermostat or
Evolution Communication User Interface. With a call for first

stage cooling, the outdoor fan, reversing valve, and low stage
compressor are energized. If low--stage cannot satisfy cooling

demand, high--stage cooling is energized by the second stage of

indoor thermostat or User Interface. After second stage is satisfied,
the unit returns to low--stage operation until first stage is satisfied

or until second stage is required again. When both first stage and
second stage cooling are satisfied, the compressor will shut off. The

reversing valve will remain energized until the control board power

is removed or a call for heating in initiated. With a call for heating,
the outdoor fan and compressor are energized. The compressor will

operate in high or low stage operation, as needed to meet the
heating demand. When the heating demand is satisfied, the

compressor and fan will shut off. The reversing valve is

de--energized in the heating mode.

NOTE

: When two--stage unit is operating at low--stage, system

vapor (suction) pressure will be higher than a standard single--stage
system or high--stage operation.

NOTE

:

Outdoor fan motor will continue to operate for one

minute after compressor shuts off, when outdoor ambient is greater
than or equal to 100

°

F. This reduces pressure differential for easier

starting on next cycle.

NOTE

: On 286A models, if unit has not operated within the past

12 hours, or following a unit power--up, upon the next thermostat
high-- or low--stage demand, unit operates for a minimum of 5
minutes in high--stage.
With non--communicating (non--Evolution) systems, with first
stage of cooling, Y1 and O are powered on; and with second stage

of cooling, Y1, Y2, and O are on. For these systems, with first

stage of heating Y1 is on and for second stage of heating, Y1 and
Y2 are on. When the reversing valve is energized, O is powered

on.

Communication and Status Function Lights

For Evolution Control only, Green communications (COMM)

Light

A green LED

(COMM light)

on the outdoor board (see Fig. 6)

indicates successful communication with the other system

products. The green LED will remain OFF until communication is
established. Once a valid command is received, the green LED will

turn ON continuously. If no communication is received within 2

minutes, the LED will be turned OFF until the next valid
communication.

Amber Status Light

An amber colored

STATUS light

is used to display the operation

mode and fault codes as specified in the troubleshooting section.

See Table 6 for codes and definitions.

NOTE

: Only one code will be displayed on the outdoor unit

control board (the most recent, with the highest priority).

Utility Interface

With Evolution Control

The utility curtailment relay should be wired between R and Y2
connections on the control board for Evolution Communicating

Systems only (see Fig. 6.) This input allows a power utility device
to interrupt compressor operation during peak load periods. When

the utility sends a signal to shut the system down, the User

Interface will display, “Curtailment Active”.

286A

/288A

Summary of Contents for Evolutiont 286A

Page 1: ...rmation This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could resul...

Page 2: ...nt tubing sets metering device and filter drier listed in presale literature There can be no deviation Consult the Service Manual Air Conditioners and Heat Pumps Using Puron Refrigerant to obtain required unit changes for specific applications and for R 22 retrofit Check Equipment and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit Inspect Equipment File cl...

Page 3: ...outdoor unit Make Piping Connections WARNING PERSONAL INJURY AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal injury or death Relieve pressure and recover all refrigerant before system repair or final unit disposal Use all service ports and open all flow control devices including solenoid valves CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in e...

Page 4: ...rd with Evolution Control Low Ambient not allowed with non communicating thermostat No No Compressor Start Assist Capacitor and Relay Standard on 286A models Not required for 288A Standard on 286A models Not required for 288A Standard on 286A models Not required for 288A Low Ambient Control Standard with Evolution Control Low ambient not allowed with non communicating thermostat No No Support Feet...

Page 5: ...rant Tubing and Indoor Coil CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Never use the system compressor as a vacuum pump Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns The alternate triple evacuation method may be used See Service Manual for triple evacuation method Alw...

Page 6: ...nstructions packaged with kits or accessories when installing Make Airflow Selections Airflow Setup for Evolution Control Furnace of FE Fan coil communicating When using an Evolution User Interface airflow is automatically selected based on equipment size See User Interface Installation Instructions for available adjustments Airflow Selection for Variable Speed Furnaces for Non Communicating non E...

Page 7: ...mand high stage cooling is energized by the second stage of indoor thermostat or User Interface After second stage is satisfied the unit returns to low stage operation until first stage is satisfied or until second stage is required again When both first stage and second stage cooling are satisfied the compressor will shut off The reversing valve will remain energized until the control board power...

Page 8: ...put for both high and low stage equals the value for low stage opera tion below 55_F 12 8_C Time Delays The unit time delays include S Five minute time delay to start cooling or heating operation when there is a call from the thermostat or user interface To bypass this feature momentarily short and release Forced Defrost pins S Five minute compressor re cycle delay on return from a brown out condi...

Page 9: ...odels the PWM output for both high and low stage equals the value for low stage operation below 55_F 12 8_C Defrost This control offers 5 possible defrost interval times 30 60 90 120 minutes or AUTO These are selected by dip switches on the unit control board or by the Evolution Control User Interface The Evolution Control selection overrides the control board dip switch settings AUTO defrost adju...

Page 10: ...e solenoid should be installed near the outdoor unit with the arrow facing the outdoor unit This is the direction of flow control See application manual for long line application details Accessory Liquid Solenoid with Evolution Communicating Control When using the Evolution Control the liquid line solenoid output is provided at the Y1 connection Connect the solenoid as shown in the wiring label di...

Page 11: ...and serial information If the factory control board fails the model plug must be transferred from the original board to the replacement board for the unit to operate NOTE The model plug takes priority over factory model information input at the factory If the model plug is removed after initial power up the unit will operate according to the last valid model plug installed and flash the appropriat...

Page 12: ...t sensed when the compressor should be starting the appropriate contactor may be stuck open or there is a wiring error The control will flash the appropriate fault code Check the contactor and control box wiring 286A Models Only Compressor Start Detection on Models with Bristol Compressors Only In low stage if the specified start voltage at VR terminal is not achieved the start relay is de energiz...

Page 13: ... performed during low ambient cooling or defrost operation Failed Thermistor Default Operation Factory defaults have been provided in the event of failure of outdoor air thermistor OAT and or outdoor coil thermistor OCT If the OAT sensor should fail low ambient cooling will not be allowed and the one minute outdoor fan off delay will not occur Defrost will be initiated based on coil temperature an...

Page 14: ...relay and capacitor held in circuit too long if installed High Stage Thermal Cutout 72 Compressor operation detected then disappears while high stage demand exists Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long if installed Contactor Shorted 73 Compressor voltage sensed when no demand for compressor operation exists Contactor may be stuc...

Page 15: ... W1 W2 Heat Cool Stage 1 Y1 W2 Y1 Heat Cool Stage 2 Y Y2 Y Y2 Y Y2 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DHUM 24VAC Common C COM C Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor Variable Speed Furnace Thermidistat 2 Stage Heat Pump Indicates connection may not be...

Page 16: ...e hoses with 700 psig service pressure rating 12 Leak detectors should be designed to detect HFC refrigerant 13 Puron refrigerant as with other HFCs is only compatible with POE oils 14 Vacuum pumps will not remove moisture from oil 15 Do not use liquid line filter driers with rated working pressures less than 600 psig 16 Do not leave Puron refrigerant suction line filter driers in line longer than...

Reviews: