background image

12

and OCT faults will not be cleared. The code will continue to be
flashed.
The control is shipped with the brownout active. The change in
status is remembered until toggled to a new status. A power

down/power up sequence will not reset the status. It may be

necessary to do the toggle twice to cycle to the desired state of the
defeat.

230V Line (Power Disconnect) Detection

If there is no 230v at the compressor contactor(s) when the indoor
unit is powered and cooling or heating demand exists, the

appropriate fault code is displayed. Verify the disconnect is closed
and 230v wiring is connected to the unit.

Compressor Voltage Sensing

The control board input terminals labeled VS, VR and L2 on 286A

models and VS and L2 on 288A models (see Fig. 6) are used to
detect compressor voltage status and alert the user of potential

problems. The control continuously monitors the high voltage on
the run capacitor of the compressor motor. Voltage should be

present any time the compressor contactor is energized and voltage

should not be present when the contactor is de--energized.

Contactor Shorted Detection

If there is compressor voltage sensed when there is no demand for

compressor operation, the contactor may be stuck closed or there

may be a wiring error. The control will flash the appropriate fault
code.

286A Models -- Compressor Thermal Cutout

The control senses the compressor voltage at VR and VS. When
starting or running, a phase difference of the voltages on the inputs

will indicate the thermal protector is closed. If the phase difference

is 5

_

or less for 10 seconds, the internal protector is open. The

control de--energizes the appropriate compressor contactor for 15

minutes, but continues to operate the outdoor fan. The control
Status LED will flash the appropriate code shown in Table 6. After

15 minutes, with a call for low or high stage cooling or heating, the

appropriate compressor contactor is energized. If the thermal
protector has not re--set, the outdoor fan is turned off. If the call for

cooling or heating continues, the control will energize the
compressor contactor every 15 minutes. If the thermal protector

closes, (at the next 15 minute interval check) the unit will resume

operation.
If the thermal cutout trips for three consecutive cycles, then unit

operation is locked out for 4 hours and the appropriate fault code is
displayed.

288A Compressor Thermal Cutout

If the control senses the compressor voltage after start--up and is

then absent for 10 consecutive seconds while cooling or heating
demand exists, the thermal protector is open.

The control

de--energizes the compressor contactor for 15 minutes, but
continues to operate the outdoor fan. The control Status LED will

flash the appropriate code shown in Table 6. After 15 minutes,

with a call for low or high stage cooling or heating, the compressor
contactor is energized. If the thermal protector has not re--set, the

outdoor fan is turned off. If the call for cooling or heating
continues, the control will energize the compressor contactor every

15 minutes. If the thermal protector closes, (at the next 15 minute

interval check) the unit will resume operation.
If the thermal cutout trips for three consecutive cycles, then unit

operation is locked out for 4 hours and the appropriate fault code is
displayed.

Low or High Contactor Open (286A models) / No 230V

at Compressor Contactor (288A models)

If the compressor voltage is not sensed when the compressor

should be starting, the appropriate contactor may be stuck open or
there is a wiring error. The control will flash the appropriate fault

code. Check the contactor and control box wiring.

286A Models Only -- Compressor Start Detection on

Models with Bristol Compressors Only

In low stage, if the specified start voltage at VR terminal is not

achieved, the start relay is de--energized after 1 second and the
control will flash the appropriate fault code.
In high stage, if the specified start voltage at VS terminal is not
achieved, the start relay is de--energized after 1 second and the

control will flash the appropriate fault code.
If the specified start voltage is not achieved for 3 consecutive low
stage starts, low stage operation is locked out for 30 minutes. If the

specified start voltage is not achieved for 3 consecutive high stage
starts, high stage operation is locked out for 30 minutes. The

control will flash the appropriate fault code.

Troubleshooting 286A units for proper switching

between low & high stages

Check the suction and liquid pressures at the service valves.

Suction pressure should be reduced by 5--10% when switching
from low to high capacity. There should be a 10--20% increase in

liquid pressure when switching from low to high capacity.
Compressor current should increase 100--250% when switching

from low to high stage.

Troubleshooting 288A units for proper switching

between low & high stages

Check the suction pressures at the service valves. Suction pressure
should be reduced by 3--10% when switching from low to high

capacity.

NOTE

: The liquid pressures are very similar between low and

high stage operation, so liquid pressure should not be used for
troubleshooting.
Compressor current should increase 20--45% when switching from
low to high stage. The compressor solenoid when energized in

high stage, should measure 24vac.
When the compressor is operating in low stage the 24v DC

compressor solenoid coil is de--energized. When the compressor is

operating in high stage, the 24v DC solenoid coil is energized. The
solenoid plug harness that is connected to the compressor HAS an

internal rectifier that converts the 24v AC signal to 24v DC.

DO

NOT INSTALL A PLUG WITHOUT AN INTERNAL

RECTIFIER.

Unloader Test Procedure

The unloader is the compressor internal mechanism, controlled by
the DC solenoid, that modulates between high and low stage. If it

is suspected that the unloader is not working, the following
methods may be used to verify operation.

1. Operate the system and measure compressor amperage.

Cycle the unloader on and off at 30 second plus intervals at

the UI (from low to high stage and back to low stage). Wait
5 seconds after staging to high before taking a reading. The

compressor amperage should go up or down at least 20 per-
cent.

2. If the expected result is not achieved, remove the solenoid

plug from the compressor and with the unit running and the
UI calling for high stage, test the voltage output at the plug

with a DC voltmeter. The reading should be 24 volts DC.

3. If the correct DC voltage is at the control circuit molded

plug, measure the compressor unloader coil resistance. The
resistance should be 32 to 60 ohms depending on com-
pressor temperature. If the coil resistance is infinite, much

lower than 32 ohms, or is grounded, the compressor must
be replaced.

Temperature Thermistors

Thermistors are electronic devices which sense temperature. As the
temperature increases, the resistance decreases. Thermistors are

used to sense outdoor air (OAT) and coil temperature (OCT).

Refer to Fig. 7 for resistance values versus temperature.

286A

/288A

Summary of Contents for Evolutiont 286A

Page 1: ...rmation This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could resul...

Page 2: ...nt tubing sets metering device and filter drier listed in presale literature There can be no deviation Consult the Service Manual Air Conditioners and Heat Pumps Using Puron Refrigerant to obtain required unit changes for specific applications and for R 22 retrofit Check Equipment and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit Inspect Equipment File cl...

Page 3: ...outdoor unit Make Piping Connections WARNING PERSONAL INJURY AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal injury or death Relieve pressure and recover all refrigerant before system repair or final unit disposal Use all service ports and open all flow control devices including solenoid valves CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in e...

Page 4: ...rd with Evolution Control Low Ambient not allowed with non communicating thermostat No No Compressor Start Assist Capacitor and Relay Standard on 286A models Not required for 288A Standard on 286A models Not required for 288A Standard on 286A models Not required for 288A Low Ambient Control Standard with Evolution Control Low ambient not allowed with non communicating thermostat No No Support Feet...

Page 5: ...rant Tubing and Indoor Coil CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Never use the system compressor as a vacuum pump Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns The alternate triple evacuation method may be used See Service Manual for triple evacuation method Alw...

Page 6: ...nstructions packaged with kits or accessories when installing Make Airflow Selections Airflow Setup for Evolution Control Furnace of FE Fan coil communicating When using an Evolution User Interface airflow is automatically selected based on equipment size See User Interface Installation Instructions for available adjustments Airflow Selection for Variable Speed Furnaces for Non Communicating non E...

Page 7: ...mand high stage cooling is energized by the second stage of indoor thermostat or User Interface After second stage is satisfied the unit returns to low stage operation until first stage is satisfied or until second stage is required again When both first stage and second stage cooling are satisfied the compressor will shut off The reversing valve will remain energized until the control board power...

Page 8: ...put for both high and low stage equals the value for low stage opera tion below 55_F 12 8_C Time Delays The unit time delays include S Five minute time delay to start cooling or heating operation when there is a call from the thermostat or user interface To bypass this feature momentarily short and release Forced Defrost pins S Five minute compressor re cycle delay on return from a brown out condi...

Page 9: ...odels the PWM output for both high and low stage equals the value for low stage operation below 55_F 12 8_C Defrost This control offers 5 possible defrost interval times 30 60 90 120 minutes or AUTO These are selected by dip switches on the unit control board or by the Evolution Control User Interface The Evolution Control selection overrides the control board dip switch settings AUTO defrost adju...

Page 10: ...e solenoid should be installed near the outdoor unit with the arrow facing the outdoor unit This is the direction of flow control See application manual for long line application details Accessory Liquid Solenoid with Evolution Communicating Control When using the Evolution Control the liquid line solenoid output is provided at the Y1 connection Connect the solenoid as shown in the wiring label di...

Page 11: ...and serial information If the factory control board fails the model plug must be transferred from the original board to the replacement board for the unit to operate NOTE The model plug takes priority over factory model information input at the factory If the model plug is removed after initial power up the unit will operate according to the last valid model plug installed and flash the appropriat...

Page 12: ...t sensed when the compressor should be starting the appropriate contactor may be stuck open or there is a wiring error The control will flash the appropriate fault code Check the contactor and control box wiring 286A Models Only Compressor Start Detection on Models with Bristol Compressors Only In low stage if the specified start voltage at VR terminal is not achieved the start relay is de energiz...

Page 13: ... performed during low ambient cooling or defrost operation Failed Thermistor Default Operation Factory defaults have been provided in the event of failure of outdoor air thermistor OAT and or outdoor coil thermistor OCT If the OAT sensor should fail low ambient cooling will not be allowed and the one minute outdoor fan off delay will not occur Defrost will be initiated based on coil temperature an...

Page 14: ...relay and capacitor held in circuit too long if installed High Stage Thermal Cutout 72 Compressor operation detected then disappears while high stage demand exists Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long if installed Contactor Shorted 73 Compressor voltage sensed when no demand for compressor operation exists Contactor may be stuc...

Page 15: ... W1 W2 Heat Cool Stage 1 Y1 W2 Y1 Heat Cool Stage 2 Y Y2 Y Y2 Y Y2 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DHUM 24VAC Common C COM C Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor Variable Speed Furnace Thermidistat 2 Stage Heat Pump Indicates connection may not be...

Page 16: ...e hoses with 700 psig service pressure rating 12 Leak detectors should be designed to detect HFC refrigerant 13 Puron refrigerant as with other HFCs is only compatible with POE oils 14 Vacuum pumps will not remove moisture from oil 15 Do not use liquid line filter driers with rated working pressures less than 600 psig 16 Do not leave Puron refrigerant suction line filter driers in line longer than...

Reviews: