background image

1

607C

PREFERRED

t

14 SEER

SINGLE--PACKAGED HEAT PUMP SYSTEM WITH PURON

r

(R--410A) REFRIGERANT SINGLE AND THREE PHASE

NOMINAL 2--5 TONS (SIZES 024--060)

Installation Instructions

NOTE

:

Read the entire instruction manual before starting the

installation.

NOTE

:

Installer: Make sure the Owner’s Manual and Service

Instructions are left with the unit after installation.

TABLE OF CONTENTS

PAGE

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . . .

INTRODUCTION

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

RECEIVING AND INSTALLATION

2--9

. . . . . . . . . . . . . . . . . .

Check Equipment

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Identify Unit

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Inspect Shipment

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Provide Unit Support

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Roof Curb

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Slab Mount

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Ground Mount

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Provide Clearances

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Rig and Place Unit

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Inspection

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Use of Rigging Bracket

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Select and Install Ductwork

6

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Converting Horizontal Discharge Units to Downflow
(Vertical) Discharge Units

8

. . . . . . . . . . . . . . . . . . . . . . . . . .

Provide for Condensate Disposal

8

. . . . . . . . . . . . . . . . . . . . . .

Install Electrical Connections

8

. . . . . . . . . . . . . . . . . . . . . . . . .

High--Voltage Connections

8

. . . . . . . . . . . . . . . . . . . . . . . . .

Special Procedures for 208--V Operation

9

. . . . . . . . . . . . . . .

Control Voltage Connections

9

. . . . . . . . . . . . . . . . . . . . . . . .

Standard Connections

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Transformer Protection

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Accessory Electric Heaters Installation

9

. . . . . . . . . . . . . . . .

607C Sequence of Operation

9

. . . . . . . . . . . . . . . . . . . . . . . .

PRE--START--UP

15

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

START--UP

15--17

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Checking Cooling & Heating Control Operation

15

. . . . . . . .

Check for Refrigerant Leaks

15

. . . . . . . . . . . . . . . . . . . . . . . . .

Start--Up Adjustments

15

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Checking & Adjusting Refrigerant Charge

16

. . . . . . . . . . . .

Indoor Airflow & Airflow Adjustments

16

. . . . . . . . . . . . . .

Continuous Fan Operation

16

. . . . . . . . . . . . . . . . . . . . . . . .

Defrost Control

17

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Quiet Shift

17

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Defrost

17

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

MAINTENANCE

18--23

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Air Filter

18

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Indoor Blower and Motor

18

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Outdoor Coil, Indoor Coil, & Condensate Drain Pan

20

. . . . . .

Outdoor Fan

21

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Electrical Controls and Wiring

21

. . . . . . . . . . . . . . . . . . . . . . .

Refrigerant Circuit

21

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Indoor Airflow

21

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Metering Devices-- TXV & Piston

21

. . . . . . . . . . . . . . . . . . . .

Pressure Switches

22

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Loss of Charge Switch

22

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

High Pressure Switch

22

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Copeland Scroll compressor (Puron Refrigerant)

22

. . . . . . . . .

C99062

Fig. 1 -- Unit 607C

Refrigerant System

22

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Refrigerant

22

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Compressor Oil

22

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Servicing Systems on Roofs with Synthetic Materials

22

. . . .

Liquid Line Filter Drier

23

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Puron

R

(R--410A) Refrigerant Charging

23

. . . . . . . . . . . . .

System Information

23

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Loss of Charge Switch

23

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Check Defrost Thermostat

23

. . . . . . . . . . . . . . . . . . . . . . . . .

TROUBLESHOOTING

23

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

START--UP CHECKLIST

23

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Installation and servicing of this equipment can be hazardous due
to mechanical and electrical components. Only trained and

qualified personnel should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance functions such
as cleaning and replacing air filters. All other operations must be

performed by trained service personnel. When working on this
equipment, observe precautions in the literature, on tags, and on

labels attached to or shipped with the unit and other safety

precautions that may apply.
Follow all safety codes. Installation must be in compliance with

local and national building codes. Wear safety glasses, protective
clothing, and work gloves. Have fire extinguisher available. Read

these instructions thoroughly and follow all warnings or cautions

included in literature and attached to the unit.

Recognize safety information. This is the safety--alert symbol

.

When you see this symbol on the unit and in instructions or manu-

als, be alert to the potential for personal injury. Understand these

signal words: DANGER, WARNING, and CAUTION. These
words are used with the safety--alert symbol. DANGER identifies

the most serious hazards which

will

result in severe personal injury

or death. WARNING signifies hazards which

could

result in per-

Summary of Contents for 607C024

Page 1: ...Piston 21 Pressure Switches 22 Loss of Charge Switch 22 High Pressure Switch 22 Copeland Scroll compressor Puron Refrigerant 22 C99062 Fig 1 Unit 607C Refrigerant System 22 Refrigerant 22 Compressor...

Page 2: ...The slab should extend approximately 2 in 51 mm beyond the casing on all 4 sides of the unit Do not secure the unit to the slab except when required by local codes Ground Mount The unit may be install...

Page 3: ...he brackets to the unit PROPERTY DAMAGE HAZARD Failure to follow this warning could result in personal injury death or property damage Rigging bracket MUST be under the rain lip to provide adequate li...

Page 4: ...4 A08084 Fig 2 607C024 030 Unit Dimensions 607C...

Page 5: ...5 A08085 Fig 3 607C036 060 Unit Dimensions 607C...

Page 6: ...c heaters require 90 degree elbow in supply duct WARNING When designing and installing ductwork consider the following 1 All units should have field supplied filters or accessory filter rack installed...

Page 7: ...BTyp Supply opening B x C Long Support D 445 16 Return opening B X C Insulated deck pan Short Support CTyp bracket 1126 mm C00076 UNIT SIZE CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM 607C024 030...

Page 8: ...ield supplied 3 4 in PVC or field supplied 3 4 in copper pipe at outlet end of the 2 in 51 mm trap See Fig 11 Do not undersize the tube Pitch the drain trough downward at a slope of at least 1 in 25 m...

Page 9: ...rmostat through the control wiring inlet hole grommet Fig 2 and 3 and into the low voltage splice box Provide a drip loop before running wires through panel Secure and strain relief all wires so that...

Page 10: ...0 11x10 279x254 3 4 1400 11x10 279x254 3 4 1600 11x10 279x254 1 0 1750 11x10 279x254 1 0 HIGH PRESSURE SWITCH psig Cutout Reset Auto 650 15 420 25 LOSS OF CHARGE LOW PRESSURE SWITCH Liquid Line psig C...

Page 11: ...11 Duct Covers C00092 Fig 10 607C with Duct Covers On Shown with optional louvers 1 25 mm MIN 2 51 mm MIN TRAP OUTLET A08001 Fig 11 Condensate Trap 607C...

Page 12: ...12 A08024 Fig 12 Wiring Schematics 208 230 1 60 607C...

Page 13: ...13 A08025 Fig 13 Wiring Schematics 208 230 3 60 607C...

Page 14: ...14 A08026 Fig 14 Wiring Diagram 460 3 60 607C...

Page 15: ...the unit for proper control operation as follows 1 Place room thermostat SYSTEM switch or MODE control in OFF position Observe that blower motor starts when FAN mode is placed in FAN ON position and s...

Page 16: ...efrigerant leak refer to Check for Refrigerant Leaks section Indoor Airflow and Airflow Adjustments All 607C blower motors are factory wired for nominal cooling airflow operation at minimum external s...

Page 17: ...control which includes a field selectable time period DIP switch 1 and 2 on the board between defrost cycles of 30 60 90 or 120 minutes factory set at 60 minutes To initiate a forced defrost two optio...

Page 18: ...eplace the filter with the same dimensional size and type as originally installed See Table 1 for recommended filter sizes Inspect air filter s at least once each month and replace throwaway type or c...

Page 19: ...2292 2238 2158 2049 1935 1840 1732 1635 1513 Air delivery values are without air filter and are for dry coil See 607C Wet Coil Pressure Drop Table 1 Factory shipped cooling heat pump heating speed NOT...

Page 20: ...ith a mild detergent and water solution Rinse coils with clear water using a garden hose Be careful not to splash water on motors insulation wiring or air filter s For best results spray condenser coi...

Page 21: ...ontrols and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper operation If discrepancies are observed in operating cycle or if a suspected m...

Page 22: ...amic suction or discharge valves and it is more tolerant of stresses caused by debris liquid slugging and flooded starts The compressor is equipped with an internal pressure relief port The pressure r...

Page 23: ...evice wired into control circuit low voltage It shuts off the compressor if abnormally low pressures are present in the refrigeration circuit NOTE Because these switches are attached to refrigeration...

Page 24: ...driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE o...

Page 25: ...Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restriction in refrigerant sys...

Page 26: ...OLTAGE __________________________________ COMPRESSOR AMPS_________________________________ INDOOR EVAPORATOR FAN AMPS___________ TEMPERATURES OUTDOOR CONDENSER AIR TEMPERATURE ___________DB RETURN AIR...