Air 70 Rev. D
33
Chapter 13 Setting values
DESCRIPTION
FACTORY
SETTING
SETTING RANGE
STEP
Most recently set ventilation mode
2
1, 2, 3, 4 or 5
1
Ventilation mode 1
15 m
3
/h
15 m
3
/h - 70 m
3
/h
1 m
3
/h
Ventilation mode 2
25 m
3
/h
15 m
3
/h - 70 m
3
/h; but higher than set value mode 1
1 m
3
/h
Ventilation mode 3
40 m
3
/h
15 m
3
/h - 70 m
3
/h; but higher than set value mode 2
1 m
3
/h
Ventilation mode 4
55 m
3
/h
15 m
3
/h - 70 m
3
/h; but higher than set value mode 3
1 m
3
/h
Ventilation mode 5
70 m
3
/h
15 m
3
/h - 70 m
3
/h; but higher than set value mode 4
1 m
3
/h
Bypass temperature
22.0°C
15.0°C - 35.0°C
0.5°C
Operation bypass
0
0 (= Bypass automatic)
1 (= Bypass permanently inactive)
2 (= Bypass permanently active)
0D[LPXP¿OWHUÀRZ
54000 m
3
/h
0 - 200000 m
3
/h
1000 m
3
/h
Bypass temperature hysteresis
2.0 °C
0.0°C - 5.0°C
0.5°C
DESCRIPTION
FACTORY
SETTING
PLUS PCB
SETTING RANGE
STEP
Sensitivity
RH sensor
0
+2
most sensitive
+1
Ĺ
0
basic setting RH sensor
-1
Ļ
-2
least sensitive
Low setting CO
2
sensor
400
400 - 1200 ppm
25 ppm
High setting CO
2
sensor
1200
400 - 1200 ppm
25 ppm
Bus address
8
0 - 8 (0 = Master)
1
Slave number
0
0 - 4
0 = master
1 - 4 = slave number
1
MODBUS slave adres
11
1 t/m 247
1
MODBUS speed
4
0 - 3
1
MODBUS parity
1
0 - 2
1
MODBUS interface
1
0 - 2
1
Set values when using the Brink service tool
:KHQFRQQHFWLQJWKH%ULQNVHUYLFHWRROYDULRXVVHWYDOXHVFDQEHPRGL¿HG7KHVHUYLFHWRROPXVWEHFRQQHFWHGWRWKH$LUVHUYLFH
connector.
5HIHUWRWKHWDEOHEHORZIRUVHWYDOXHVWREHPRGL¿HG
0 = 9600 Baud/ 1 = 19k2 Baud (default)
2 = 38k4 Baud/ 3 = 56k Baud
0 = No parity (extra stopbit)
1 = Even parity (default, 1 stopbit)
2 = Odd parity (1 stopbit)
0 = not supported
1 = Air 70 (default)
2 = not supported