16
BRIGGSandSTRATTON.COM
Initial Start-up (No Load)
Beforeoperatingthehomegeneratororplacingitinto
service,inspecttheentireinstallationcarefully.
Thenbegintestingthesystemwithoutanyelectricalloads
connected,asfollows:
1. Setgenerator’smaincircuitbreakertoits
ON
(closed)
position.
. Install15Ampfuseincontrolpanel.
3. Setgenerator’ssystemswitchto
AUTO
.
4. Push
MANUAL OVER-RIDE
buttononcontrolpanel.
NOTE
:Whenthehomegeneratorisstartedforthevery
firsttime,itwillrequirethatairinthegaseousfuellinesbe
purged.Thismaytakeafewminutes.
5. DONOTcrankengineformorethan10seconds,then
pausefor10secondstoreduceheatinthestarter.
6. Repeatprocessuntilenginestarts.
7. Listenforunusualnoises,vibrationorotherindications
ofabnormaloperation.Checkforoilleakswhileengine
runs.
8. Letenginewarmupforaboutfiveminutestoallow
internaltemperaturestostabilize.
9. ConnectanaccurateACvoltmeterandafrequency
metertocheckgeneratoroutputatloadsideofcircuit
breaker.Voltageshouldbe39-6Volts,frequency
shouldbe6.0-6.5Hz.
NOTE
:Ifeitherparameterisoutsidetheseranges,perform
theEngineAdjustmentsdescribedbelow.
10. Checkgeneratoroutputbetweenoneofthegenerator
connectionlugsandtheneutrallug,thenbetweenthe
othergeneratorconnectionlugandtheneutrallug.
Inbothcases,voltagereadingshouldbebetween
119-131Volts.
11. Pushandhold
MANUAL OVER-RIDE
buttononcontrol
panelagainuntilenginestops.
IMPORTANT
:DONOTproceeduntilyouarecertainthat
generatorACvoltageandfrequencyarecorrectandwithin
thestatedlimits.Toobtainthepropergeneratorfrequency,
see
Engine Adjustments
.
Engine Adjustment
Eachhomegeneratorunitleavesthefactorysetforeither
NGorLPgasoperation.Thereareregionalvariancesinthe
compositionofnaturalgas.Ifthegeneratoroutputvoltage
orfrequencymeasuredduringInitialStart-Up(paragraph#9)
isoutsidethelistedranges,thecombustibilityofthegas
suppliedattheinstallationsitemaybesubstantiallydifferent
fromthefuelusedatthefactory.
Toadjusttheengineforthisdifference,proceedasfollows.
1. Opentheoildrainandcontrolpanelaccessdoors.
. Removethefourscrewsthatholdthecircuitbreaker
covertotheairintakeguard.
3. Connectanaccuratefrequencymetertothelinesideof
thegenerator’smaincircuitbreaker.
4. Ensurethatthe15Ampfuseisinstalled.
5. Setthegenerator’smaincircuitbreaker
ON
.
6. Setthegenerator’ssystemswitchto
AUTO
.
7. Push
MANUAL OVER-RIDE
buttononcontrolpanel.
Whentheenginestarts,allowittowarmupforfive
minutes.
Summary of Contents for 202826GS
Page 1: ...Installation Start Up Manual Home Generator System Manual No 202826GS Rev D 05 02 2008...
Page 18: ...18 BRIGGSandSTRATTON COM Schematic...
Page 19: ...19 Wiring Diagram...
Page 21: ...Manual de Instalaci n y Arranque Generador dom stico...
Page 39: ...Manuel d Installation et D marrage G n ratrice r sidentielle...