Page 78
B
RADFORD
W
HITE
16
Internal fault:
Safety relay test failed due to safety
relay OFF
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
17
Internal fault:
Safety relay test failed due to safety
relay not OFF
L
18
Internal fault:
Safety relay test failed due to
feedback not ON
L
19
Internal fault:
Safety RAM write
L
20
Internal fault:
Internal fault: Flame ripple and
overfl ow
H
21
Internal fault:
Flame number of sample mismatch
H
22
Internal fault:
Flame bias out of range
H
23
Internal fault:
Bias changed since heating cycle
starts
H
24
Internal fault:
Spark voltage stuck low or high
H
25
Internal fault:
Spark voltage changed too much during
fl ame sensing time
H
26
Internal fault:
Static fl ame ripple
H
27
Internal fault:
Flame rod shorted to ground detected
H
28
Internal fault:
A/D linearity test fails
H
29
Internal fault:
Flame bias cannot be set in range
H
30
Internal fault:
Flame bias shorted to adjacent pin
H
31
Internal fault:
SLO electronics unknown error
H
32-46
Internal fault:
Safety Key 0 through 14
L
47
Flame Rod to ground leakage
H
48
Static fl ame (not fl ickering)
H
49
24 VAC voltage low/high
H
1. Check the module and display connections.
2. Check the module power supply and make
sure that frequency, voltage and VA meet the
specifi cations.
Code
Description
Lockout
or Hold
Procedure
Summary of Contents for Copper Brute II BWCH 2000
Page 4: ...BRADFORD WHITE...
Page 26: ...Page 22 BRADFORD WHITE 150 285 Figure 23 Minimum Venting Distance...
Page 48: ...Page 44 BRADFORD WHITE Figure 38 Ladder Diagram 7 9 Ladder Diagram...
Page 96: ...Page 92 BRADFORD WHITE Parts Illustration 4 Internal Components Sizes 750 850...
Page 98: ...Page 94 BRADFORD WHITE Parts Illustration 6 Gas Train Components Sizes 600 850...
Page 102: ...Page 98 BRADFORD WHITE Notes...
Page 103: ...Page 99 Brute HIGH EFFICIENCY COMMERCIAL BOILERS AND VOLUME WATER HEATERS Notes...