Page 77
Brute
HIGH EFFICIENCY COMMERCIAL BOILERS AND VOLUME WATER HEATERS
11.2 Troubleshooting Table
This table includes a listing of the fault codes that may be displayed. Some of these can be corrected by
changing a parameter, while other conditions are more complicated, and will require a service technician.
The fi rst column lists the code number that will appear at the beginning of the Lockout or Hold message in
the orange bar at the bottom of the screen. The second column lists the text as it will appear on the Touch
Screen. The third column shows whether the condition will cause a Hold, or Lockout, or both. The fourth
column lists some suggestions for corrective action.
Code
Description
Lockout
or Hold
Procedure
1
Unconfi gured safety data
L
1. New device, complete device confi guration and
safety verifi cation.
2. If fault repeats, replace module
2
Waiting for safety
data verifi cation
L
1. Device in Confi guration mode and safety
parameters need verifi cation and a device needs
reset to complete verifi cation.
2. Confi guration ended without verifi cation, re enter
confi guration, verify safety parameters and reset
device to complete verifi cation.
3. If fault repeats, replace module.
3
Internal fault:
Hardware fault
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
4
Internal fault:
Safety Relay key feedback error
H
5
Internal fault:
Unstable power (DC DC) output
H
6
Internal fault:
Invalid processor clock
H
7
Internal fault:
Safety relay drive error
H
8
Internal fault:
Zero crossing not detected
H
9
Internal fault:
Flame bias out of range
H
10
Internal fault:
Invalid burner control state
L
11
Internal fault:
Invalid burner control state fl ag
L
12
Internal fault:
Safety relay drive cap short
H
13
Internal fault:
PII (Pre-Ignition Interlock) shorted
to ILK (Interlock)
H or L
15
Internal fault:
Safety relay test failed due to
feedback ON
L
Summary of Contents for Copper Brute II BWCH 2000
Page 4: ...BRADFORD WHITE...
Page 26: ...Page 22 BRADFORD WHITE 150 285 Figure 23 Minimum Venting Distance...
Page 48: ...Page 44 BRADFORD WHITE Figure 38 Ladder Diagram 7 9 Ladder Diagram...
Page 96: ...Page 92 BRADFORD WHITE Parts Illustration 4 Internal Components Sizes 750 850...
Page 98: ...Page 94 BRADFORD WHITE Parts Illustration 6 Gas Train Components Sizes 600 850...
Page 102: ...Page 98 BRADFORD WHITE Notes...
Page 103: ...Page 99 Brute HIGH EFFICIENCY COMMERCIAL BOILERS AND VOLUME WATER HEATERS Notes...