Page 52
B
RADFORD
W
HITE
Menu 20. CH Setpoint source
Choose S2 (J8-6) 4-20 mA, then press OK
Then scroll over to the Modulation sub-menu and
click onto Modulation rate source.
Select Local, then press OK.
8.7.3 Outdoor Reset Configuration
At this sub-menu, confirm that Central Heat is Enabled.
Next, press onto the Maximum Outdoor Temperature,
Minimum Outdoor Temperature, and Low Water
Temperature to get to each and adjusting their setpoints in
those sub-menus.
8.7.4 DHW - Domestic Hot Water
Configuration
DHW - Domestic Hot Water is used to configure the
DHW temperature parameters for water heaters (NTV)
and for indirect water heaters that are used with boiler
(NTH) systems.
Press on the Setpoint box to get to the adjustment sub-
menu. Then adjust it up or down to your desired DHW
setpoint.
8.7.5 Warm Weather Shutdown
Configuration
From this sub-menu you will be able to enable/disable the
Warm Weather Shutdown feature and adjust the set
point.