Page 70
B
RADFORD
W
HITE
3.
Observe all warnings on the Operating Instructions
label and turn on the gas and main electrical power
(circuit breaker) to the unit.
4.
If the unit has the optional gas pressure switches, the
low pressure gas switch will need to be reset.
5.
Turn the Brute on at the On/Off switch.
6.
The Brute unit will begin the start sequence. The
blower and pump will energize for the pre-purge
period, then the ignition sequence will start. After all
safety devices have been verified, the gas valve will
open. If ignition doesn’t occur, turn off the Brute, and
check that there is proper gas supply. Wait 5 minutes
before restarting.
7.
Follow Section 8.10 for set up of Combustion Mixture.
8.
After placing the appliance in operation, the Burner
Safety Shutoff Device must be tested
:
•
Close the gas shutoff valve with the burner operating.
•
The flame will go out and the blower will
continue to run for the post purge cycle. One
or three additional attempts to light will follow.
Each cycle will include pre-purge, ignitor on,
valve/flame on, and post purge. Ignition will
not occur because the gas is off. The ignition
control will lockout after a single try or a third try
depending on the controller model.
•
Open the gas shutoff valve. Reset the boiler
control by pressing the Reset button on the
control or on the display. If the unit has the
optional gas pressure switches, you will need
to reset the low pressure switch. Find the low
pressure switch and press the reset button. Restart
the appliance. The ignition sequence will start
again and the burner will start. The appliance will
return to its previous mode of operation.
DANGER
If you detect any odor of gas, or if the gas burner
does not appear to be functioning in a normal
manner, CLOSE THE MAIN SHUTOFF VALVE.
Do not shut off the switch. Contact your heating
contractor, gas company, or factory representative.
9.3 Shutting Down the Brute Unit
1.
Turn off the main electrical disconnect switch.
2.
Close all manual gas valves.
3.
If you think the Brute unit might freeze, drain it. All
water must be removed from the heat exchanger, or
damage from freezing may occur. Also be sure to
protect the piping in the building from freezing.
Caution
This step must be performed by a qualified service
person.
9.4 Restarting the Brute Unit
If the unit has been drained, see Section 9.1 in this
manual for instructions on filling and purging the unit
properly, before continuing.
1.
Turn off the main electrical disconnect switch.
2.
Close all manual gas valves.
3.
WAIT FIVE (5) MINUTES.
4.
Set the aquastat or thermostat to its lowest setting.
5.
Open all manual gas valves.
6.
Reset all safety switches (low pressure gas switch,
manual reset high limit, etc.).
7.
Set the temperature controller to the desired
temperature setting, and switch on electrical power.
8.
The burner will go through a prepurge period followed
by ignition.
Summary of Contents for Copper Brute II BWCH 2000
Page 4: ...BRADFORD WHITE...
Page 26: ...Page 22 BRADFORD WHITE 150 285 Figure 23 Minimum Venting Distance...
Page 48: ...Page 44 BRADFORD WHITE Figure 38 Ladder Diagram 7 9 Ladder Diagram...
Page 96: ...Page 92 BRADFORD WHITE Parts Illustration 4 Internal Components Sizes 750 850...
Page 98: ...Page 94 BRADFORD WHITE Parts Illustration 6 Gas Train Components Sizes 600 850...
Page 102: ...Page 98 BRADFORD WHITE Notes...
Page 103: ...Page 99 Brute HIGH EFFICIENCY COMMERCIAL BOILERS AND VOLUME WATER HEATERS Notes...