RE 30139-B/12.14 | VT-HNC100...X
Bosch Rexroth AG
21/
48
Assembly
6.2 Recommended accessories
The following accessories are recommended for the connection of the
VT-HNC100...3X axis control. These accessories are not included in the scope of
delivery, and can be ordered separately at Bosch Rexroth.
Table 6: Accessories
Component
Material number
RS232 interface cable, 1:1, length: 3 m
R900776897
USB RS232 converter
R901066684
Cable set VT17220-1X/HNC100...3X, length 2 m, for analog
signals (connection X2A) and digital position measurement
systems (connection X8M) with HD connector and open breakout
cable for:
VT-HNC100-1-3X, VT-HNC100-2-3X,
VT-HNC100-3-3X, VT-HNC100-4-3X
R901189300
Cable set VT17220-1X/HNC100...3X, length 2 m,for analog
signals (connection X2A) and digital position measurement
systems (connection X8M) with FK MC connector and open
breakout cable for: VT-HNC100-C-3X
R901189302
Plug-in connector Type 6ES7972-0BA42-0XA0 for PROFIBUS DP
R901312863
6.3 VT-HNC100...3X assembly
f
Lay the cables and lines so that they cannot be damaged and no one can trip
over them.
f
By snapping the housing of the VT-HNC100...3X/ on a conductive assembly
rail, the earth connection to the control cabinet rear wall is established. This
constitutes the HF earthing of the VT-HNC100...3X.
f
No silicone-containing sealing, adhesive, or insulating agents must be used.
f
Ensure a maintenance-friendly installation, i.e. simple access to the
connection lines. Free access to the connection side must be guaranteed.
f
Before installation note down the information on the nameplates. If, after the
installation, nameplates are no longer visible or legible, these data will be
quickly available to you at any time.
6.3.1 Place of installation
Do not install the HNC next to power electronics (e.g. frequency converters, etc.)
The power pack of the VT-HNC100...3X should be installed as close to the
VT-HNC100...3X as possible.
6.3.2 Voltage supply
f
The connection should be as short as possible. Pass supply and
return lines (+24 V/GND) together. Voltage 18-30 V with residual ripple
< 1.5 Vpp, I = 1 A - 4 A (depends on the HNC variant and the additional
supplied components).
•
Load lines of two individual wires (e.g. voltage supply) are to be passed in a
parallel or drilled form.