RE 30139-B/12.14 | VT-HNC100...X
Bosch Rexroth AG
25/
48
Assembly
Max. length of the cable: 2 m
NOTE
: On the side of the breakout cable, all wires must be connected to the
terminal strip. Otherwise there is a risk of short circuit!
The earthing of the control cabinet must be considered accordingly.
wiring diagram for analog (X2A) or digital interface (X8M)
VT17220-1X/HNC100...3X & material number: R90118930
0
Fig. 7: wiring diagram for analog or digital interface
1
HD sub connector high density 15-pole with solder bucket
2
D-SUB housing, 9-pole, metal/UNC (Mat. no. R900016918)
3
Shrinkable tubing 30 mm
4
Cable Unitronic LiYCY 8 x 2 x 0.14 mm
2
, approx. 2.2 m
5
Shrinkable tubing 40 mm
6
Wire end ferrules
NOTE
: Type and manufacturer of item 2 are binding (housing dimensions)!
1
2
3
4
5
6
Provide litz wire
with pos. 6 wire
end ferrules
Shield put over outer
sheath
Shrink shield onto cable sheath
using a shrinkable tubing
Printed on the cable on both ends (smear-resistant), text height 3 mm