RE 30139-B/12.14 | VT-HNC100...X
Bosch Rexroth AG
27/
48
Assembly
wall, i.e the earth. The low-resistance connection of the conductibly coated
DIN rail taddo the control cabinet rear wall is important.
2
VT-HNC100...3X Compact shield system
The cable shields are connected with the VT-HNC100 housing via the shield
pin of the Micro Combicon connector. The connection to the control cabinet
rear wall is established via the housing and the DIN rail.
An intermediate terminal block with shield strip must be used. See illustration
below.
Fig. 9: Micro-Combicon connector and open cable end
wiring diagram for analog (X2A) or digital interface (X8M)
VT17220-1X/HNC100...3X & material number: R901189302
Fig. 10: wiring diagram for analog or digital interface
1
8-pole Micro Combicon connector FK-MC 0.5/-ST-2.5
2
Shrinkable tubing 30 mm
3
Unitronic LiYCY cable 4 x 2 x 0.25 mm
2
, approx. 2.2 m long
4
Shrinkable tubing 40 mm
5
Wire end ferrules
Black litz wire soldered to the shield
Printed on the cable on both ends (smear-resistant, text height 3 mm)
Provide litz wires
with pos. 5 wire end
ferrules
Shrink shield onto cable sheath
using a shrinkable tubing
Shield put over outer
sheath
Shrink black litz wire
after soldering
1
2
3
4
5