Menu settings INSTALLER SETTINGS (for installers only)
|
85
US/CA
8.10 Test of the actuators on the
system
INSTALLER SETTINGS: Output test
The
Output test
menu gives you the opportunity
to activate individual actuators (pumps, mixing
valves) individually to check their function.
•
Stop all output tests
: Use this parameter to
reset the activation of all actuators to
Auto
.
•
Pump, heating circuit 1
:
–
Auto
: Control of the pump according to the
set program
–
Manual ON
: Pump always on
–
Manual OFF
: Pump off
•
Pump, heating circuit 2
: See above under
Pump, heating circuit 1
•
Mixer, heating circuit 1
:
–
Auto
: Control of the mixing valve according
to the set program
–
Manual 100 % open
: Mixing valve in open
position
–
Manual 50 % open
: Mixing valve in middle
position
–
Manual 0 % open
: Mixing valve in closed
position
•
Mixer, heating circuit 2
: See above under
Mixer, heating circuit 1
•
Tank charge pump
: See above under
Pump,
heating circuit 1
•
DHW recirculation pump
: See above under
Pump, heating circuit 1
For menu structure and adjustment range
Æ
page 65.
As long as one or several actuators
are activated manually, a
corresponding message will be
shown on the display.