6 720 643 256 (2010/05)
84
|
Menu settings INSTALLER SETTINGS (for installers only)
US/CA
•
Total slab drying time
:
–
The minimum total duration (3) is
automatically calculated by the heating
controls. This is based on a rise of supply
temperature of a maximum 18 °F (10 °C)
per day.
–
A higher value must be entered for the
whole duration (3) if the slab cannot bear
this increase. This produces a
corresponding reduction in the daily
increase.
–
The first stage and the last stage of the
supply temperature is 78 °F (25 °C) (fixed
value).
Example:
Maximum supply temperature (1) =
122 °F (50 °C)
Duration of maximum supply temperature (2) =
7 days
Max. increase/decrease in temperature
per day = 9 °F (5 °C)
Total duration of slab drying (3) = 17 days
•
Start date
: Enter the start date of the slab
drying here.
•
Start time
: Enter the start time of the slab
drying here.
Fig. 28
1d
1 day
1
Maximum supply temperature
2
Duration of max. supply temperature
3
Total duration of slab drying
4
Start date and start time
t
Time
VL
Supply temperature
For menu structure and adjustment range
Æ
page 65.
2d
122
°
F 77
°
F
–
(
)
9
°
F
------------------------------------------
×
7d 17d
=
+
2d
50
°
C 25
°
C
–
(
)
5K
----------------------------------------
×
7d
+
17d
=
25
3
5
45
77
95
11
3
°C
°F
1d
1d
1d
1d
t
6 720 64
3
250-14.1O
3
4
2
1