Menu settings INSTALLER SETTINGS (for installers only)
US/CA
8.2 Configuring the heating system
Installer settings: System configuration
For menu structure and adjustment ranges
Æ
page 58.
Use this menu if you want to configure the system
automatically or manually. E.g. on commissioning
the system for the first time or making changes to
it.
•
Start automatic system configuration
for
starting automatic configuration.
•
DHW configuration
for manual configuration
of the domestic hot water system.
•
Maximum tank temperature
: This menu
option is only available if tank is in use.
•
DHW recirculation pump
: This menu option is
only active if the domestic hot water system
has a hot water recirculation pump.
•
Heating circuit 1 configuration
for
configuring the heating circuit 1.
•
Heating circuit 1 remote control
for
deactivating or activating the remote control
on the heating circuit 1.
•
Heating circuit 2 configuration
for
configuring the heating circuit 2.
•
Heating circuit 2 remote control
for
deactivating or activating the remote control
on the heating circuit 2.
•
ISM 2
for heating systems with solar hot water
system or heating boost.
When first commissioning a heating system,
proceed as follows:
B
Set ID of all BUS devices according to their
function (e.g. IPM2 for heating circuit 1 and
heating circuit 2, etc.).
B
Start automatic configuration.
B
Check the other menu options under
System
configuration
and, if necessary, adjust to suit
the present system.
For menu structure and adjustment ranges
Æ
page 58.
For system examples, see the
instructions for the IPM Other
examples can be found in the
planning documents.
WARNING:
Danger of scalding if
the tank temperature is higher than
140 °F (60 °C).
B
If the tank temperature limit is
set > 140 °F (> 60 °C) install a
thermostatic water mixer in the
hot water supply.
B
Set the domestic hot water
mixer unit to 140 °F max.
(60 °C).
The heating system's solar thermal
system must be configured
manually (
Æ
Section 8.4, page 72).
Automatic configuration of the
heating system does not configure
the solar system.