6 720 643 256 (2010/05)
Menu settings INSTALLER SETTINGS (for installers only)
|
61
US/CA
8.1.4 INSTALLER SETTINGS: Solar sys parameters
Menu structure
Solar sys parameters
Default
setting
Control range
Personal
setting
Description
starts
on page
1. Standard system
–
–
–
73
SP: ON delta T
14 °F
(8 °C)
6 °F ... 36 °F (3 °C ... 20 °C)
(not lower than “SP: OFF delta T”
+2 °F (+1 °C))
°F ( °C)
SP: OFF delta T
8 °F (4 °C) 4 °F ... 34 °F (2 °C ... 19 °C)
(not higher than “SP: ON delta T” –
2 °F ( – 1 °C))
°F ( °C)
T2: Max. solar tank
temperature
140 °F
(60 °C)
Disabled (<60 °F or <15 °C) |
60 ... 194 °F (15 °C ... 90 °C)
°F ( °C)
Maximum collector
temperature
248 °F
(120 °C)
212 °F ... 284 °F (100 °C ... 140 °C)
°F ( °C)
SP: Collector field 1 pump
mode
Auto
Auto | Manual ON | Manual OFF
2. Heating support
–
–
–
74
DWU1: ON delta T
10 °F
(6 °C)
6 °F ... 36 °F (3 °C ... 20 °C)
(not lower than “DWU1: OFF delta T”
+2 °F (+1 °C)
°F ( °C)
DWU1: OFF delta T
6 °F (3 °C) 4 °F ... 34 °F (2 °C ... 19 °C)
(not higher than “DWU1: ON
delta T” – 2 °F ( – 1 °C))
°F ( °C)
DWU1: High return valve
mode
Auto
Auto | Manual ON | Manual OFF
DWU1: High return valve
switch signal
Not
reversed
Not reversed | Reversed
A collector field 2
–
–
–
75
PA: ON delta T
14 °F
(8 °C)
6 °F ... 36 °F (3 °C ... 20 °C)
(not lower than “PA: OFF delta T”
+2 °F (+1 °C)
°F ( °C)
PA: OFF delta T
8 °F (4 °C) 4 °F ... 34 °F (2 °C ... 19 °C)
(not higher than “PA: ON delta T” –
2 °F ( – 1 °C))
°F ( °C)
PA: Collector field 2 pump
mode
Auto
Auto | Manual ON | Manual OFF