Panel Controller
Bypass | en
57
Bosch Sicherheitssysteme GmbH
User Guide
2017.09 | 7.0 | F.01U.258.929
6.
Select
Bypass
.
The selected elements are bypassed.
In the
Bypass
field on the status bar, the number of bypassed elements is increased by
two elements.
To remove the bypass from the elements, repeat all previous steps but select
Un- bypass
in
step 6.
Notice!
Depending on the configuration and the structure of the panel, it is possible that signaling
devices cannot be bypassed individually but only all at once. In this case, the
NACAll
list field
is offered in step 4 instead of the selection list.
12.3
Displaying and un-bypassing bypassed element groups
1.
There are two ways to display all partly or completely bypassed loops, logical zones etc.:
–
Select
Bypass
on the status bar
A list of various states is displayed. Or
–
Select
Bypass Block
in the start menu.
2.
Select either
Bypassed
or
Bypass
and then
Show bypassed devices
.
A list of various element categories is displayed. The listed number displays the number
of bypassed elements or element groups in the relevant element category.
3.
Select the list field you require, e.g. logical zone.
4.
Select:
–
Partly bypassed
to display all partly bypassed logical zones
–
Completely bypassed
to display all completely bypassed logical zones
Depending on which option you select, all partly bypassed or fully bypassed logical zones
will be displayed. The number in parentheses, e.g. (5) specifies the number of bypassed
elements.
To remove the bypass from all elements in one or more logical zones, select the logical
zone you require and select
Un- bypass
.
12.4
Displaying list of all bypassed elements
There are two ways to display a list of all bypassed elements:
–
Using the menu, page 57
–
Via the status bar, page 58
12.4.1
Using the menu
To display a list of all bypassed elements, select the following in the start menu:
1.
Bypass Block
2.
Bypass
3.
Show bypassed devices
A list of various element categories is displayed. The listed number displays the number
of bypassed elements or element groups in the relevant element category.
4.
Select the element category you require, e.g.
Detector
.
A list of all bypassed detectors is displayed:
To un-bypass bypassed elements:
1.
Select the element you require.
2.
Select
Un- bypass
.
The element is un-bypassed.