Diagnostics
Diagnostics information and help materials for pinpointing problems in a network can be
found under menu item
Diagnostics
-
Network
. Information is provided on the following
topics:
–
Routing table
Information concerning the accessibility of all nodes within the system network via the
respective interface.
–
Ethernet ports
Information concerning different parameters and the status of the two Ethernet
interfaces available at the panel controller.
–
Send ping command
Sending of a ping command to a specific IP address to check the availability of other
nodes in the network.
–
Consistency check
The check performed determines whether the Ethernet configuration from FSP-5000-RPS
corresponds to the configuration entered at the panel controller. In the event of
discrepancies, a fault message is displayed.
–
Ethernet redundancy
Information concerning the type of redundancy configuration (RSTP or dual-homing). In
the case of redundancy via RSTP, the RSTP parameters of the RSTP panel and those of
the root bridge are displayed.
Further information can be found in Network services, page 64.