Applications Manual FHP560 Controller
| 29
Bosch Thermotechnology Corp.
Data subject to change
Page____ of ____
Integration Points
#
Point Description
Name
BACnet
MODBUS
N2
LON
Read
Only
Description
Name
Type
ID
Object
Type
Register
Type
ID
SNVT
#
Name
SNVT
26
Zone Temperature
eff_zone_temp_1
AV:7
fl
oat value
40057
data
fl
oat
29
‒
‒
‒
Effective Zone Temperature Status
in °F
27
Hot Gas Reheat
Modulating Valve Status
eff_hgr_mod_vlv1_1
AV:28
fl
oat value
40005
data
fl
oat
14
19
nvoEffHgrModVlv1
SNVT_lev_
percent(81)
Effective Hot Gas Reheat
Modulating Valve Output Status
28
Static Air Fan Speed
eff_sa_fan_speed_1
AV:55
fl
oat value
40007
data
fl
oat
15
20
nvoEffSaFanSpeed
SNVT_lev_
percent(81)
Effective Static Air Fan Speed in %
29
Supply Air Duct Static
Pressure
eff_sa_sta_press_1
AV:53
fl
oat value
40009
data
fl
oat
17
‒
‒
‒
Effective Static Air Pressure Sensor
Status in H2O"
30
Zone CO
₂
Level
eff_zn_CO
₂
_lev_1
AV:25
fl
oat value
40065
data
fl
oat
33
‒
‒
‒
Effective Zone CO
₂
Levels in PPM
31
Compressor Enabled
Stages
enabled_clstages_1
AV:68
fl
oat value
40023
data
fl
oat
27
‒
‒
‒
Compressor Stages Enabled
32
Input Expansion Module
Mode
iem_mode_1
AV:50
fl
oat value
40085
data
fl
oat
63
‒
‒
‒
IEM Con
fi
guration Setup
0 = Dirty Filter Switch, Fan Status
Switch, Valve End Switch
(Default)
1 = Smoke Detector Switch, Fan
Status Switch, Valve End
Switch
2 = Dirty Filter Switch, Fan Status
Switch, Differential Pressure
Switch
3 = Smoke Detector Switch, Fan
Status Switch, Dirty Filter
Switch
4 = Dirty Filter Switch, Fan Status
Switch, Damper End Switch
5 = Smoke Detector Switch, Fan
Status Switch, Secondary
Drain Pan
6 = Dirty Filter Switch, Fan Status
Switch, Pump Status Switch
7 = None
33
BAS Relative Humidity
Enable/Disable
rh_bas_sel_1
AV:51
fl
oat value
40109
data
fl
oat
80
57
nviRhBasSel
SNVT_count_
inc(9)
RH Sensor Source Selection
0 = BAS RH Sensor
1 = Hard-Wired RH Sensor
(Default)
34
Heating Demand
Percentage
htg_pct_1
AV:12
fl
oat value
40073
data
fl
oat
37
‒
‒
‒
Heating Capacity in %
35
Mix Air Temperature
Source Status
mat_sel_status_1
AV:84
fl
oat value
40025
data
fl
oat
30
‒
‒
‒
Mixed Air Temperature Sensor
Source Status
0 = BAS MAT
1 = Wired MAT"
36
Mixed Air Temperature
Sensor
mat_sel_1
AV:85
fl
oat value
40019
data
fl
oat
31
‒
‒
‒
Mixed Air Temperature Sensor
Source Setup
0 = BAS MAT Sensor
1 = Hard-Wired MAT Sensor
(Default)
37
Minimum Damper
Position
min_mdpr_pos_1
AV:79
fl
oat value
40079
data
fl
oat
40
‒
‒
‒
Minimum Damper Position Setup
Default = 10% Open
38
Analog Output 2
Options Con
fi
guration
ao2_cfg_sel_1
AV:83
fl
oat value
40089
data
fl
oat
65
52
nviAo2CfgSel
SNVT_count_
inc(9)
Options Con
fi
guration - Controller
Analog Output #2 (AO-2)
0 = Not Used (Default)
1 = Modulating Hot Gas Reheat
Valve Control
Table 25
Integration Points
#
Point Description
Name
BACnet
MODBUS
N2
LON
Read
Only
Description
Name
Type
ID
Object
Type
Register
Type
ID
SNVT
#
Name
SNVT
39
Analog Output 1
Options Con
fi
guration
ao1_cfg_sel_1
AV:82
fl
oat value
40087
data
fl
oat
64
51
nviAo1CfgSel
SNVT_count_
inc(9)
Options Con
fi
guration - Controller
Analog Output #1 (AO-1)
0 = Not Used (Default)
1 = Variable Frequence Drive Signal
Control
2 = Mixed Air SCR Preheat Control
3 = SCR Controlled Aux Electric
Heat
40
Mixed Air Temperature
Setpoint
mat_stpt_1
AV:90
fl
oat value
40021
data
fl
oat
32
‒
‒
‒
Mixed Air Temperature Setpoint
Default: 42 °F, Minimum: 40°F,
Maximum: 60°F
41
Unit Mode Status
mode_status_1
AV:24
fl
oat value
40027
data
fl
oat
34
25
nvoModeStatus
SNVT_count_
inc(9)
Unit Mode of Operation Selection
Status
0 = Cooling only
1 = Aux Heat
2 = Heat Pump
3 = Heat Pump + Aux Heat
4 = Heat Pump + Hot Gas Re-Heat
5 = C Hot Gas Re-Heat"
42
Single Reset/
Free Cooling Reset
Temperature
oat_reset1_1
AV:69
fl
oat value
40027
data
fl
oat
35
‒
‒
‒
Outside Air Temperature (Free
Cooling Temperature) Operation in
°F or Single Reset Temperature
Default: 50 °F
43
Part Cool Reset
Temperature
oat_reset2_1
AV:72
fl
oat value
40029
data
fl
oat
36
‒
‒
‒
Outside Air Temperature (Stage 1
Cooling Temperature) Operation
in °F
Default: 60 °F
44
Full Cool Reset
Temperature
oat_reset3_1
AV:74
fl
oat value
40033
data
fl
oat
38
‒
‒
‒
Outside Air Temperature (Stage 2
Cooling Temperature) Operation
in °F
Default: 75 °F
45
Heating Reset
Temperature
oat_reset_ht_1
AV:92
fl
oat value
40035
data
fl
oat
39
‒
‒
‒
Outside Air Temperature Reset
Mixed Air (Stage 1 Heating)
Operation in °F
Default: 40 °F
46
Temperature Reset
Mode
oat_rst_mode_1
AV:71
fl
oat value
40037
data
fl
oat
41
‒
‒
‒
Outside Air Temperature Reset
Setup
0 = Single
1 = Multiple (Default)
47
Outside Air
Temperature Sensor
oat_sel_1
AV:73
fl
oat value
40041
data
fl
oat
42
‒
‒
‒
Outside Air Temperature Sensor
Source Setup
1 = BAS OAT Sensor
2 = Hard-Wired OAT Sensor
(Default)
48
Outside Air
Temperature Sensor
Source Status
oat_sel_sta_1
AV:78
fl
oat value
40029
data
fl
oat
43
‒
‒
‒
Outside Air Temperature Sensor
Source Status
0 = BAS OAT Source
1 = Hard-Wired OAT Source
49
Setpoint
occ_clg_stpt_1
AV:4
fl
oat value
40103
data
fl
oat
52
9
nviOccClgStpt
SNVT_
temp_p(105)
Occupied Cooling Setpoint Setup
in °F
Default: 74 °F
50
Setpoint
occ_htg_stpt_1
AV:2
fl
oat value
40105
data
fl
oat
53
10
nviOccHtgStpt
SNVT_
temp_p(105)
Occupied Heating Setpoint Setup
in °F
Default: 70 °F
Table 26