4 2 |
FHP560 Controller
Applications Manual
Bosch Thermotechnology Corp.
Data subject to change
Page____ of ____
To make the zone warmer or cooler using a ZS Pro:
1. From the Home screen, press the
or
button to show the Setpoint Adjustment screen. The screen shows the following:
Fig. 17
2. Press
the
or
button to adjust the zone temperature setpoint. The control program determines how much you can adjust the setpoint
and is default to +/- 3°F. The FHP560 control program allows this adjustment value to be changed either using a BACview interface or from an
available BAS. The maximum allowable setpoint adjustment from the space is +/- 10°F.
3. Any setpoint adjustments made during an occupied session are cleared each time the unit transitions from occupied mode to unoccupied
mode, and the setpoint adjustment remains at 0 until the next manual adjustments in the space.
4. Wait a few seconds until the display returns to the home screen before you press any other buttons.
To override the schedule using a ZS Pro:
Timed override to an occupied state
1. Press
the button one time to override the schedule and put the zone in an occupied state for a length of time speci
fi
ed in the control
program.
2. Press
the
button to incrementally increase the time. The time increases in increments of 30 minutes and the maximum length of time that
the override may be scheduled is 3 hours.
3. To cancel an override and return control to the schedule, press the button twice.
4. Wait a few seconds until the display returns to the home screen before you press any other buttons. During the override, the bottom of the
display shows the time (minutes) remaining in the override and an hourglass to indicate the override state.
Fig. 18
Force to an unoccupied state
1. Press and hold the button for 3 seconds to force the zone to an unoccupied state.
2. To cancel the force to unoccupied and return control to the schedule, press the button again.
To lock the sensor buttons of a ZS Pro:
1. Simultaneously press and hold the 2 buttons shown below for 5 seconds to lock the sensor’s buttons. The display shows a lock icon to
indicate the locked state.
Fig. 19
2. Press and hold the 2 buttons again for 5 seconds to unlock the buttons.
If you press the button slightly before the
button,
the sensor will go into an override state instead of
locking the buttons. But, if you press the
button
fi
rst,
the buttons will lock.
To edit displayed values using a ZS Pro:
If the display shows a value other than a zone temperature setpoint with to the right of it, the value is editable from the sensor.
An example is the screen for the zone humidity setpoint. Access this screen by pressing the info button several times (approx 7 times) until the
humidity setpoint is visible (Rnet tag 406), then follow the steps below to change the value as needed (max of 95%rh, min of 20%rh):
1. Press
the
or
button to adjust the value.
2. Wait until the display returns to the home screen before you press any other buttons.
If the control program speci
fi
es that the value is not
editable, you will see
without arrows.