Applications Manual FHP560 Controller
| 43
Bosch Thermotechnology Corp.
Data subject to change
Page____ of ____
14.12 Rnet Tags
Rnet tags are numbers that identify types of system values, and determine how the ZS sensor will display those values. For example:
The Rnet tag number 100 indicates Fan Status. The sensor will display a fan icon when the microblock is active.
The Rnet tag number 416 indicates Air Flow Setpoint. Values such as this that do not have an icon will display the Rnet tag number in the
lower left corner of the sensor’s display.
Fig. 20
Below is a list of information provided by the ZS Pro Combo Sensor when the info button is pressed:
Information Displayed When Info Button is Pressed
Press info button this
number of times
Information Displayed
Rnet Tag Number
Read Only
Inactive Text
Active Text
1*
Occupied Cooling Setpoint
n/a
2
Occupied Heating Setpoint
n/a
3
Unoccupied Cooling Setpoint
n/a
4
Unoccupied Heating Setpoint
n/a
5
Effective Cooling Setpoint
n/a
6
Effective Heating Setpoint
n/a
7
Occupied Zone Humidity Setpoint
406
8
Outdoor Air Temperature (OAT)
300
9
Aux Heat Output Command
1102
Off
On
10
Effective Discharge Air Temperature (DAT)
304
11
Leaving Water Temperature (LWT)
319
12
Current Alarm Condition/Code
1300
13
Zone Mode Status
501
14
Compressor Stage 1 Status
1100
C1 Off
C1 On
15
Compressor Stage 2 Status
1101
C2 Off
C2 On
16
Economizer Mode Status
116
Econ Off
Econ On
Table 46
*
If there’s an active alarm(s) condition, pressing the info button once will
fi
rst display the alarm page including the corresponding Rnet tag and a short
text, before resuming the regular cycle of functions.
Alarm conditions are indicated by the bell symbol appearing on the Pro sensor display:
Fig. 21
The following is a description of the available alarm codes on the “Current Alarm Condition/Code” screen (Rnet tag 1300):
Available Alarm Codes
Alarm Code
Description
0
System Normal - No Alarms
1
UPM code for High Pressure on circuit #1 fault
2
UPM code for Low Pressure on circuit #1 fault
3
UPM code for High Pressure on circuit #2 fault
4
UPM code for Low Pressure on circuit #2 fault
5
UPM code for Water Coil Freeze on circuit #1 fault
6
UPM code for High Condensate fault
7
UPM code for Brownout fault
8
UPM code for Air Coil Freeze on circuit #1 fault
9
UPM code for Water Coil Freeze on circuit #2 fault
10
UPM code for Air Coil Freeze on circuit #2 fault
20
FHP560 Input/Output in MANUAL lock position
30
Wired Sensor Failure for ZS Sensor, DAT Sensor, LWT Sensor, Humidity Sensor or CO
₂
Sensor
40
High or Low Leaving Water Temperature (LWT) Condition
50
High or Low Zone Temperature Condition
60
High or Low Discharge Air Temperature (DAT) Condition
70
Filter or Compressor Runtime Alert
80
High or Low Zone Humidity Condition
90
High Zone CO
₂
Condition
100
Differential Pressure Switch (DPS) Open Condition
Table 47
If an alarm is generated for any of the below conditions, pressing the info button will show a short “active text” and Rnet tag:
Alarm Active Text and Rnet Tag Number:
Alarm Display Information
Rnet Tag Number
Active Text
Filter Change Status
1027
FILTER
Low Zone Temp Alarm
1026
Lo ZTp
High Zone CO
₂
Alarm
1043
Hi CO
₂
High Zone Humidity Alarm
1044
Hi RH
Low Zone Humidity Alarm
1045
Lo RH
Compressor1 Runtime Alarm
1050
C1 RT
Compressor2 Runtime Alarm
1051
C2 RT
High Discharge Air Temp Alarm
1028
Hi DAT
Low Discharge Air Temp Alarm
1029
Lo DAT
Manual I/O Lock Alarm
1116
IO OVRD
Wired Sensor Faliure Alarm
1115
SEN Conn
High Leaving Water Temp Alarm
1113
Load H2O
Low Leaving Water Temp Alarm
1114
Load H2O
High Zone Temp Alarm
1025
Hi ZTp
DPS Lock Alarm
1117
DPS
UPM General High Pressure Alarm
1118
HP Fault
UPM General Low Pressure Alarm
1119
LP Fault
UPM General Freezestat Alarm
1120
Frz stat
UPM Brownout BRN Alarm
1109
Brn Out
UPM Condensate COND Alarm
1108
Hi Cond
Table 48