Integration Points
#
Point Description
Name
BACnet
MODBUS
N2
LON
Read
Only
Description
Name
Type
ID
Object
Type
Register
Type
ID
SNVT
#
Name
SNVT
88
Outdoor RH low limit
for Air Econ
rh_lo_lim_aecon_1
AV:119
fl
oat value
40119
data
fl
oat
89
‒
‒
‒
Air Economizer Option: range
setting for Outside Air Relative
Humidity (Low Limit) in %
Default: 40 %
89
Compressor Status
comp_state_1
AV:120
fl
oat value
40053
data
fl
oat
90
‒
‒
‒
√
Reports compressor state for heat
pump units:
0 = Normal/Off
1 = Compressor Locked
2 = Compressor Overriden ""ON""
3 = Compressor Shutdown/Alarm
90
SCR Electric Heat
Output
mat_pid_1
AV:121
fl
oat value
40055
data
fl
oat
91
‒
‒
‒
SCR controlled Electric Heat
Output in %
91
Alarm Status
alm_status_1
BV:24
discrete in
10002
binary in
2
30
nvoAlmStatus
SNVT_
switch(95)
Network Status indicating alarm
condition in unit (see ""Current
Alarm"" for more information)
0 = System Normal
1 = System in Alarm"
92
Aux Heat Output Cmd
aux_htg_cmd_1
BV:20
discrete in
10003
binary in
3
31
nvoAuxHtgCmd
SNVT_
switch(95)
Auxiliary Heat Output Status
0 = Aux Heat Off
1 = Aux Heat On
93
UPM Safety - Brownout
Alarm
brn_2st_1
BV:10
discrete in
10004
binary in
4
32
nvoBrn2st
SNVT_
switch(95)
Brown Out Alarm Status
0 = Normal
1 = BRN Alarm Enabled
94
Occupancy Command
(BAS)
occupancy_cmd_1
BV:1
discrete out
1
binary out
1
12
nviOccupancyCmd
SNVT_
switch(95)
BAS Occupancy Command
0 = Unoccupied (Default)
1 = Occupied (Enables Unit
Operation)
95
Compressor 1 Runtime
comp1_rntm_1
BV:35
discrete in
10006
binary in
6
‒
‒
‒
Compressor 1 Runtime Alarm
0 = Normal
1 = Timer Has Expired
(Default: >8760 Hours)
96
Compressor 2 Runtime
comp2_rntm_1
BV:36
discrete in
10007
binary in
7
‒
‒
‒
Compressor 2 Runtime Alarm
Status
0 = Normal
1 = Timer Has Expired
(Default: >8760 Hours)
97
Compressor 1 Runtime
Reset
cmp1_rntm_rst_1
BV:13 discrete out
2
binary out 10
35
nviCmp1RntmRst
SNVT_
switch(95)
Compressor 1 Runtime Reset.
Momentary On/Off required.
0 = Reset Off (Default)
1 = Reset On
98
Compressor 2 Runtime
Reset
cmp2_rntm_rst_1
BV:14 discrete out
3
binary out 11
36
nviCmp2RntmRst
SNVT_
switch(95)
Compressor 2 Runtime Reset.
Momentary On/Off required.
0 = Reset Off (Default)
1 = Reset On
99
Comp Stage1 Output
Cmd
cmp_stg1_cmd_1
BV:11
discrete in
10008
binary in
8
33
nvoCmpStg1Cmd
SNVT_
switch(95)
Compressor Stage 1 Output Status
0 = Compressor 1 Off
1 = Compressor 1 On
100
Comp Stage2 Output
Cmd
cmp_stg2_cmd_1
BV:12
discrete in
10009
binary in
9
34
nvoCmpStg2Cmd
SNVT_
switch(95)
Compressor Stage 2 Output Status
0 = Compressor 2 Off
1 = Compressor 2 On
Table 31
Integration Points
#
Point Description
Name
BACnet
MODBUS
N2
LON
Read
Only
Description
Name
Type
ID
Object
Type
Register
Type
ID
SNVT
#
Name
SNVT
101
UPM Safety - High
Condensate Alarm
con_2st_1
BV:9
discrete in
10010
binary in
12
37
nvoCon2st
SNVT_
switch(95)
Condensate Drain Alarm
0 = Normal
1 = Alarm Active
102
Secondary Condensate
Pump Alarm
conpump_1
BV:50
discrete in
10012
binary in
14
‒
‒
‒
Secondary Condensate Pump
Alarm
0 = Normal
1 = Alarm Active
103 Continuous Fan
cont_fan_1
BV:18 discrete out
5
binary out 15
38
nviContFan
SNVT_
switch(95)
Con
fi
gures Fan Operation for
Continuous or Auto
0 = Cycle Fan with Compressor
Operation (Auto)
1 = Continuous Fan Operation
when Occupied or in NSB
(Default)
104
Economizer Cooling
Command
clg_econ_1
BV:92
discrete in
10015
binary in
16
‒
‒
‒
Cooling Economizer Status
0 = On
1 = Off
105
High Cooling Supply Air
Temperature in DAC
csat_hi_1
BV:86
discrete in
10016
binary in
17
‒
‒
‒
High Cooling Supply Air
Temperature during Discharge Air
Control Alarm
0 = Normal
1 = Alarm Active
106
Condenser Water Valve
Output
cwv_cmd_1
BV:79
discrete in
10017
binary in
18
‒
‒
‒
Condenser Water Valve Status
0 = Closed
1 = Open
107
Discharge Air
Temperature Sensor
da_sen_1
BV:31
discrete in
10018
binary in
19
‒
‒
‒
Discharge Air Temperature Sensor
Alarm
0 = Sensor Normal
1 = Sensor Failure Alarm
108 Damper End Switch
des_status_1
BV:93
discrete in
10019
binary in
20
‒
‒
‒
Damper End Switch Status
0 = Damper Closed
1 = Damper Open
109 Damper Command
damper_cmd_1
BV:49
discrete in
10020
binary in
21
39
nvoDamperCmd
SNVT_
switch(95)
Damper Position Output Status
0 = Closed
1 = Open
110
High Discharge Air
Temperature
dat_hi_1
BV:29
discrete in
10021
binary in
22
‒
‒
‒
Discharge Air Temperature Sensor
Alarm (High Threshold - Cooling)
0 = Normal
1 = Alarm (Default: >70 °F)
111
Discharge Air
Temperature Alarm
dat_lo_1
BV:30
discrete in
10022
binary in
23
‒
‒
‒
Discharge Air Temperature Sensor
Alarm (Low Threshold - Heating)
0 = Normal
1 = Low DAT Alarm
(Default: <75 °F)
112
Digital Override Lock
Alarm
do_lock_1
BV:37
discrete in
10023
binary in
24
‒
‒
‒
Digital Override Lock Alarm
0 = Normal
1 = Digital Override Enabled Alarm
113
Differential Pressure
Switch (DPS) Alarm
dps_alarm_1
BV:77
discrete in
10024
binary in
25
‒
‒
‒
Differential Pressure Switch Alarm
0 = Normal
1 = Alarm