Plumbing and Mechanical
VACUUM PROCESS
The default vacuum time is 10:00 minutes. When the vacuum process begins, the vacuum pump is activated. After
a 5 second delay, the vacuum solenoid activates. The HS and LS valves must be open. A timer will start when once
the vacuum transducer reading reaches 5 mBar.