BONITRON MODEL 3460 RIDE-THRU
Field start up procedure for rack systems
993001_19991022.doc
1 doc.# 993001
10/22/99
Procedure:
1. Ensure the Bonitron Ride-Thru has been properly installed.
•
Use Bonitron
Field Installation Procedure for Rack Systems
document # 993002
2. The Ride-Thru DC bus threshold must be coordinated with the under voltage trip setting of
the inverter. If the threshold is to close to the nominal bus, the Ride-Thru may supply power
to the drive continuously, and overheat. If the threshold is to close to the under voltage trip
level of the inverter, the system may not "Ride-Thru", and under voltage trips will still occur.
Most inverters have an under voltage trip point of -15% of nominal. Some inverters can be
reprogrammed to change this trip level. Bonitron typically would like the DC bus threshold
to be about -10% of the nominal bus. For example, Bonitron sets all 460VAC systems to hold
the DC bus to 590Vdc
•
Refer to your inverter's documentation for details on adjustment of the under voltage trip
setting.
•
Refer to Bonitron
"Threshold Voltage Adjustment Procedure"
document # 985001 for
details on how the Ride-Thru DC bus threshold can be changed.
3. With the Ride-Thru disconnect turned off, apply power to the system.
•
Ensure that the associated inverter is working properly
•
Confirm the under voltage trip point if possible.
4. Turn on the Ride-Thru disconnect switch and observe the following conditions on the rack
display panel:
•
DC
BUS VOLTAGE
meter should quickly rise to about 620Vdc
•
Green
POWER
LED should come
ON
•
Green
PRECHARGE COMPLETE
LED should come
ON
•
Green
RIDE-THRU READY
LED should come
ON
•
Red
RIDE-THRU ACTIVE
LED should be
OFF
•
Red
AC VOLTAGE DIP
LED should be
OFF
•
Red
HEATSINK OVERTEMP
LED should be
OFF
5. Verify DCS connection (if used).
•
DCS should read the state of the input disconnect
•
DCS should read the Ride-Thru status signals as found in the Bonitron manual section 3
•
It may be considered important to know if the Ride-Thru is not ready for the next
power dip, before it happens
•
If DCS is not used or another run signal is not used, be sure that a jumper is installed
across terminals 9 & 10 of TS2, (run command) on the 4460C board.
Summary of Contents for M3460R
Page 11: ...990078_19990803 doc ...
Page 22: ...970066P_19991230 doc ...
Page 23: ...980265P_19991230 doc ...
Page 25: ...990256_19991022 doc ...
Page 27: ...000122_20000425 doc ...
Page 29: ...990036_19990827 doc ...
Page 30: ...970104_19991025 doc ...
Page 31: ...970103_19981028 doc ...
Page 32: ...990026_19991021 doc ...
Page 33: ...990243_20000712 doc IGBT 150A 1200V IGBT 150A 1200V 150A 1200V IGBT 150A 1200V IGBT ...
Page 34: ...990244_20000712 doc ...
Page 35: ...980233_20000725 doc ...
Page 36: ...970200_20000718 doc ...
Page 37: ... SYSTEM NOTES ...