Manual EN
Electronic Circuit Breaker
V 1.0
ECONOMY SMART with IO-LINK
BLOCK Transformatoren-Elektronik GmbH
Max-Planck-Straße 36-46, 27283
.
Verden, Germany
16/2/2019 / Sch
Subject to technical changes
12
Table 4: Line cross-section: 2.5 mm²
Line length
(feed and
return line)
Inrush capacity
[mF] with 22 V
input voltage
Inrush capacity
[mF] with 24 V
input voltage
Inrush capacity
[mF] with 26 V
input voltage
Inrush capacity
[mF] with 28 V
input voltage
0
58
48
26.6
13.3
2.5
79.9
63.3
33.3
18.1
5
63.6
73.3
36.6
23.3
10
70
73.3
46.6
20
20
73
63.3
56.6
50
40
100
91.5
91.5
64.8
All capacities were determined experimentally under nominal load. The specifications are
guide values, the potential line capacities depend on the installation circumstances. The
power supply must be capable of supplying the required current without the output voltage
dropping below 18V.
3.3
Communication
The PC-0724-800-0I1 and PM-0724-400-0I1 circuit breakers communicate in accordance
with the IO-LINK standard V1.1.
An IO-LINK Master Version V1.1 is required for communication with the circuit breaker.
The circuit breakers operate in COM 3 mode (230.4 kB) and exchange 9 bytes or 13 bytes
of process data with the Master per cycle (2 ms).