Manual EN
Electronic Circuit Breaker
V 1.0
ECONOMY SMART with IO-LINK
BLOCK Transformatoren-Elektronik GmbH
Max-Planck-Straße 36-46, 27283
.
Verden, Germany
16/2/2019 / Sch
Subject to technical changes
22
4.3.3
Coding of the Circuit Breaker Status
The coding for the status of the PC-0724-800-OI1 (Index 601-608) and PM-0724-400-OI1
(Index 601-604) is shown in Table 28.
Table 28: eBreaker Status
Dec. Value
Functions
Comments
0
N.C.
Not connected
1
Switched Off
Switched off via interface
2
Switched On
Switched on
3
Tripped
Tripped
6
Current >90% Nominal
Current >90% Nominal
14
Current >100% Nominal
Current >100% Nominal
18
Tripped, Hardware Error
Hardware Error
20
Tripped, Thermal release
Thermal release
50
Switched Off, Local
Switched off locally
4.3.4
Coding of the Circuit Breaker Currents
The coding for the tripping currents of the PC-0724-800-OI1 (Index 310-318) and PM-0724-
400-OI1 (Index 310 - 313) is shown in Table 29.
Table 29: eBreaker Current
Dec. Value
Functions
Comments
0
Default
IODD DEFAULT
1000
1
Tripping current 1A
2000
2
Tripping current 2A
3000
3
Tripping current 3A
4000
4
Tripping current 4A
6000
6
Tripping current 6A
8000
8
Tripping current 8A
10000
10
Tripping current 10A