4.3.2
PM-0724-400-OI1
Acyclic I/O data is information that can be obtained directly from the circuit breaker chan-
nels, shown below in Table 27:
Table 27: Acyclic I/O Data
Index
dec
Functions
Data Type Attribute
Comments
68
eBreaker Error Code
16 Bit
RO
Error Code
69
eBreaker Type
16 Bit
RO
Device Name
70
eBreaker RC_Status 1-4
8 Bit
RO
Check bit for the
current
71
eBreaker Reset Trip Counter 1-4
8 Bit
WO
Reset the trip
counter
72
Number of Channels
8 Bit
RO
Number of Chan-
nels
73
Threshold Critical Input Voltage
Max
16 Bit
RW
Threshold UIn Max
74
Threshold Critical Input Voltage
Min
16 Bit
RW
Threshold UIn Min
75
Events PD0 - 7
8 Bit
RW
Events
81-84
eBreaker Trip Counter
8 Bit
RO
Trip Counter
100
Input Voltage
16 Bit
RO
ACTUAL Voltage IN
101 – 104
Channel Voltage 1 – 4
16 Bit
RO
ACTUAL Voltage
OUT
301 – 304
Channel Current 1 – 4
16 Bit
RO
Actual current
310 – 313
Current Settings 1 – 4
16 Bit
RW
Tripping current
601 – 604
eBreaker Status
8 Bit
RO
Status
609 – 612
eBreaker Command
8 Bit
WO
ON / OFF / RESET