Technical Manual
3-32
Range/Alternatives
Explanation and
<default value>
result of alternatives.
Menu Analog Outputs
Analog Out Source
Not in use
Gross Weight
Net Weight
Disp. Weight
Remote
< Remote >
Defines the value to represent on analog output.
Not in use: The analog output is not used.
Gross Weight: The output represents gross weight.
Net Weight: The output represents net weight.
Disp. Weight: The output represents displayed weight
Remote: The analog output value is controlled via Modbus.
Analog Out Type
+/– 20 mA
–12 – 20 mA
0-20 mA
4-20 mA
+/–10 V
0-10 V
<4-20 mA>
Defines the type of signal, used to represent the weight at this
Analog output.
+/–20mA, –12 - 20mA: bipolar current output.
0-20mA, 4-20mA: monopolar current output.
+/–10V: bipolar voltage output.
0-10V: monopolar voltage output.
Note: this parameter is not shown if parameter
Analog Out Source
is
Not in use
.
Note that in most cases some over range is available.
+/-20 mA and -12 – 20 mA ranges are limited
at -22 and +22 mA.
4 -20 mA range is limited at +4 and +22 mA.
0 -20 mA is limited at 0 and +22 mA.
+/-10 V is limited at -11 and +11V.
0–10 V is limited at 0 and +11V.
Analog Out Range Low
Range:
+/–999999
Unit:
Measurem. unit
or flow unit
<0>
Defines the weight that should give the lowest output (0 V / 0 mA
/ 4 mA) at this Analog output.
Note: this parameter is not shown if parameter
Analog Out Source
is
Not in use
or
Remote
.
Analog Out Range High
Range:
+/–999999
Unit:
Measurem. unit
or flow unit
<500>
Defines the weight that should give the highest output (10 V / 20
mA) at this Analog output.
Note: this parameter is not shown if parameter
Analog
Out Source
is
Not in use
or
Remote
.